GOLD
CGi-4E Gas-Fired Water Boiler — Boiler Manual
34
Part Number 550-110-711/1108
Start-up — operate boiler7b
DO NOT proceed with boiler
operation unless boiler and
system have been filled with
water and all instructions
and procedures of previous
manual sections have been
completed. Failure to do so
could result in severe personal
injury, death or substantial
propertydamage.Beforestart-
ing the boiler, do the follow-
ing:
• ReadmanualSection 9 and
the Operating instruction
procedure applicable for
the gas valve supplied on
theboiler(Section9c).
• Verifytheboilerandsystem
are full of water.
• VerifytheStart-up prepa-
ration
procedures of Sec-
tion 7
have been complet-
ed.
Start the boiler
• FollowtheOperating instructionsfromSection9c
to start the boiler.
• See
Section 7c if boiler fails to start.
Check system and boiler
1. Check system piping for leaks. If found, shut down
boiler and repair immediately.
2.
Vent air from system using manual vents. Air in
the system will interfere with circulation and cause
heat distribution problems and noise.
3.
Inspect vent system thoroughly for signs of
deterioration from corrosion, physical damage or
sagging.Inaddition—Checkforgas-tightsealat
every connection and seam.
If you discover evidence of any
gas leak, shut down the boiler
at once. Find the leak source
with bubble test and repair im-
mediately.Donotstartboiler
again until corrected. Failure
to comply could result in se-
vere personal injury, death or
substantial property damage.
Eliminate all system leaks.
Continualfreshmakeupwater
will reduce boiler life. Minerals
can build up in sections, reduc-
ing heat transfer, overheating
cast iron, and causing section
failure.
Glycol or antifreeze leaks
around the boiler may result
in fire, causing severe personal
injury, death or substantial
property damage.
Do not use petroleum-
based cleaning or sealing
compounds
in boiler system.
Severedamageto boilerwill
occur, resulting in substantial
property damage.
Venting system must be
sealed gas-tight
to prevent
flue gas spillage and carbon
monoxide emissions which
will result in severe personal
injury or death.
4. Check around the boiler for gas odor following the
procedureofSection7a of this manual.
5.
Verify operation perSection7b. Perform check-out
procedureinSection8, and fill in the Installation
and service certicate
on the same page.