CGi-4E Gas-Fired Water Boiler — Boiler Manual
Venting — Direct exhaust — components3c
Obtain vent system components
1. ThefollowingspecialgasventsystemscomplywithUL-1738andULC-
S636standardsandarecertiedbyCSAastheonlysystemssuitablefor
usewithCGi-4Eboilers(all3”diameter):
• Heat-Fab,Inc.
Saf-T Vent
®
• Flex-LInternational,Inc.StaR-34
• Z-Flex®,Inc.Z-Vent II
• ProTechSystemsFasNSeal™
Use only the vent starter of the same manufacturer as
theventcomponents.Donotmixcomponentsfrom
different systems. The vent system could fail, causing
flue gas spillage, resulting in severe personal injury or
death.
2. Selectventmethodbasedonpage14andinstallationrequirements.
3. Refer to
Table 4 for maximum vent run lengths and number of elbows.
DonotexceeddatainTable 4.
4. Selectventcomponentsfromseparate
Vent Supplement. All compo-
nents, including the vent starter, must be of the same vent manufacturer.
Donotmixcomponents.
Table 4 Maximum vent length (feet)
Max.vent
length (feet)
Total number of elbows
(Note 1)
1 2 3 4 5 6
CGi-4E
55 48 41 34 27 20
Note 1: Do not include termination fitting when counting total number of elbows.
ReadandfollowthespecialinstructionsfortheCom-
monwealth of Massachusetts, located on page 42 of this
manual.