Fault Reporting Function Setup
•
Fault reporting status is connected to connector
X55, output terminals 5, 6, and 7.
5.1.9 EMB2 Switches
Mode selector switch.
A panel mounted Drive/OFF/Bypass/Test selector switch is
used to electrically select whether the motor is controlled
by the drive (M1 and M2 contactors), connected to the
full-speed bypass (M3 contactor), or disconnected from
both. The test position allows for operation in bypass while
providing power to the drive (M1 and M3). See Figure 1.2.
Electromechanical Bypass (E...
5-6 BAS-SVX49A-EN