Trane Vertical Bypass/Non Bypass Panel Heating System User Manual


 
600 VAC
HP (KW)
Panel (TR200) Non Bypass &
Bypass
Non Bypass Bypass
Ground Wire
Torque lb-in (N-m)
Input Output Input Output
Drive Disconnect
Switch L1, L2, & L3
Torque lb-in (N-m)
Motor T1, T2, & T3
Torque lb-in (N-m)
Disconnect Switch
(w/o Fuses) UL508A
L1, L2, & L3 Torque
lb-in (N-m)
Disconnect Switch
Fusible UL98 L1, L2,
& L3 Torque lb-in
(N-m)
Circuit Breaker L1,
L2, & L3 Torque
lb-in (N-m)
Single Motor
Overload T1, T2, &
T3 Torque lb-in
(N-m)
15 (11)
P2
55 (6.2) 16 (1.8) 7 (.79) 17 (1.92) 62 (7) 24 (2.7) 40 (4.5)
20 (15) 55 (6.2) 16 (1.8) 7 (.79) 30 (3.3) 62 (7) 24 (2.7) 40 (4.5)
25 (18.5) 55 (6.2) 16 (1.8) 7 (.79) 30 (3.3) 62 (7) 24 (2.7) 40 (4.5)
30 (22)
P3
55 (6.2) 40 (4.5) 7 (.79) 30 (3.3) 62 (7) 50 (5.6) 40 (4.5)
40 (30) 55 (6.2) 40 (4.5) 18 (2) 30 (3.3) 62 (7) 50 (5.6) 40 (4.5)
50 (37) 55 (6.2) 40 (4.5) 18 (2) 120 (13.5) 62 (7) 50 (5.6) 40 (4.5)
60 (45)
P4
55 (6.2) 88.5 (10) 55 (6.2) 120 (13.5) 62 (7) 50 (5.6) 40 (4.5)
75 (55) 70 (7.9) 88.5 (10) 55 (6.2) 200 (22.5) 62 (7) 50 (5.6) 40 (4.5)
100 (75)
P5
200 (22.5) 124 (14) 200 (22.5) 200 (22.5) 200 (22.5) 275 (31) 40 (4.5)
125 (90) 200 (22.5) 124 (14) 200 (22.5) 200 (22.5) 200 (22.5) 275 (31) 40 (4.5)
Table 3.14 Tightening Torques, 600V
Installation
3-24 BAS-SVX49A-EN