Trane Vertical Bypass/Non Bypass Panel Heating System User Manual


 
460 VAC
HP (KW) UL Motor Current
Panel (TR200) Non Bypass
& Bypass
Maximum Field
Wiring Size Class B
or C
Field Ground
Wiring Size Class B
or C
Minimum Temperature
Wire Rating "
°
C" Copper
Conductor
15 (11) 21
P2
10 AWG 10 AWG 60
20 (15) 27 8 AWG 10 AWG 60
25 (18.5) 34 6 AWG 10 AWG 60
30 (22) 40
P3
6 AWG 10 AWG 60
40 (30) 52 4 AWG 10 AWG 60
50 (37) 65 3 AWG 8 AWG 60
60 (45) 77
P4
1 AWG 8 AWG 60
75 (55) 96 1 AWG 8 AWG 60
100 (75K) 124
P5
2/0 AWG 6 AWG 75
125 (90) 156 3/0 AWG 6 AWG 75
600 VAC
HP (KW) UL Motor Current
Panel (TR200) Non Bypass
& Bypass
Maximum Field
Wiring Size Class B
or C
Field Ground
Wiring Size Class B
or C
Minimum Temperature
Wire Rating "Degree C"
Copper Conductor
15 (11) 17
P2
10 AWG 10 AWG 60
20 (15) 22 10 AWG 10 AWG 60
25 (18.5) 27 8 AWG 10 AWG 60
30 (22) 32
P3
8 AWG 10 AWG 60
40 (30) 41 6 AWG 10 AWG 60
50 (37) 52 4 AWG 10 AWG 60
60 (45) 62
P4
3 AWG 8 AWG 60
75 (55) 77 1 AWG 8 AWG 60
100 (75) 99
P5
1 AWG 8 AWG 60
125 (90) 125 2/0 AWG 6 AWG 75
Table 3.10 Wire Size Chart 460 and 600 V
3.4.4 Wire Type Rating
The wire style rating specifications are provided inTable 3.9 and Table 3.10
3.4.5 Terminal Tightening Torques
Tighten all connections to the torque specifications provided in Table 3.11 and Table 3.13
The torque specifications are also located on the tightening torque and wire rating label inside the panel cover.
See Table 3.15 for a sample of the torque and wire rating data.
Installation
3-20 BAS-SVX49A-EN