460 VAC
HP (KW) UL Motor Current
Panel (TR200) Non Bypass
& Bypass
Maximum Field
Wiring Size Class B
or C
Field Ground
Wiring Size Class B
or C
Minimum Temperature
Wire Rating "
°
C" Copper
Conductor
15 (11) 21
P2
10 AWG 10 AWG 60
20 (15) 27 8 AWG 10 AWG 60
25 (18.5) 34 6 AWG 10 AWG 60
30 (22) 40
P3
6 AWG 10 AWG 60
40 (30) 52 4 AWG 10 AWG 60
50 (37) 65 3 AWG 8 AWG 60
60 (45) 77
P4
1 AWG 8 AWG 60
75 (55) 96 1 AWG 8 AWG 60
100 (75K) 124
P5
2/0 AWG 6 AWG 75
125 (90) 156 3/0 AWG 6 AWG 75
600 VAC
HP (KW) UL Motor Current
Panel (TR200) Non Bypass
& Bypass
Maximum Field
Wiring Size Class B
or C
Field Ground
Wiring Size Class B
or C
Minimum Temperature
Wire Rating "Degree C"
Copper Conductor
15 (11) 17
P2
10 AWG 10 AWG 60
20 (15) 22 10 AWG 10 AWG 60
25 (18.5) 27 8 AWG 10 AWG 60
30 (22) 32
P3
8 AWG 10 AWG 60
40 (30) 41 6 AWG 10 AWG 60
50 (37) 52 4 AWG 10 AWG 60
60 (45) 62
P4
3 AWG 8 AWG 60
75 (55) 77 1 AWG 8 AWG 60
100 (75) 99
P5
1 AWG 8 AWG 60
125 (90) 125 2/0 AWG 6 AWG 75
Table 3.10 Wire Size Chart 460 and 600 V
3.4.4 Wire Type Rating
•
The wire style rating specifications are provided inTable 3.9 and Table 3.10
3.4.5 Terminal Tightening Torques
•
Tighten all connections to the torque specifications provided in Table 3.11 and Table 3.13
•
The torque specifications are also located on the tightening torque and wire rating label inside the panel cover.
See Table 3.15 for a sample of the torque and wire rating data.
Installation
3-20 BAS-SVX49A-EN