27SS-PRC003-EN
Performance
Data System
Table PD-14 — Gross Cooling Capacities (MBh) - Single Compressor - TTA155C Condensing Unit with TWE155B Air Handler (I-P)
Ambient Temperature (°F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (°F)
CFMBulb616773 61 6773616773616773
Airflow (°F) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
75 94.3 92.3 103.0 67.8 112.7 43.8 91.7 91.0 99.8 66.5 108.7 42.4 88.2 88.2 96.0 64.8 104.3 41.0 84.6 84.6 91.6 62.9 99.3 39.4
4500 80 99.4 99.4 103.6 87.7 113.5 63.2 96.8 96.8 100.4 86.4 109.6 61.8 93.7 93.7 96.6 84.8 105.3 60.1 90.0 90.0 92.3 83.0 100.6 58.3
85 105.3 105.3 105.4 105.4 114.2 83.1 102.5 102.5 102.6 102.6 110.4 81.7 99.2 99.2 99.3 99.3 106.1 80.1 95.4 95.4 95.5 95.5 101.4 78.3
90 111.3 111.3 111.5 111.5 114.8 103.2 108.4 108.4 108.5 108.5 111.2 101.9 104.9 104.9 105.0 105.0 107.0 100.3 100.9 100.9 101.0 101.0 102.3 98.5
75 95.8 95.8 104.2 72.0 113.7 43.9 93.3 93.3 100.9 70.8 109.5 42.6 90.1 90.1 97.0 69.3 105.0 41.1 86.4 86.4 92.5 65.6 100.0 39.5
5000 80 101.8 101.8 104.9 92.4 114.9 66.6 99.1 99.1 101.6 91.1 110.9 65.3 95.8 95.8 97.8 89.5 106.5 63.9 92.0 92.0 93.4 87.6 101.6 62.3
85 107.9 107.9 108.0 108.0 115.4 87.3 105.0 105.0 105.0 105.0 111.6 85.9 101.5 101.5 101.6 101.6 107.2 84.3 97.6 97.6 97.6 97.6 102.3 82.5
90 114.1 114.1 114.3 114.3 116.3 109.4 111.0 111.0 111.1 111.1 112.6 108.1 107.4 107.4 107.5 107.5 108.4 106.5 103.3 103.3 103.4 103.4 103.5 103.5
75 97.7 97.7 105.2 73.3 114.5 44.7 95.0 95.0 101.8 71.9 110.2 43.4 91.8 91.8 97.8 70.2 105.6 41.9 88.0 88.0 93.2 68.2 100.4 40.3
5500 80 103.8 103.8 106.0 97.0 115.8 69.3 101.0 101.0 102.7 95.6 111.8 68.0 97.6 97.6 98.8 94.0 107.3 66.5 93.6 93.6 94.4 92.1 102.4 64.9
85 110.1 110.1 110.2 110.2 116.4 91.5 107.0 107.0 107.1 107.1 112.5 90.0 103.4 103.4 103.5 103.5 108.1 88.4 99.4 99.4 99.4 99.4 103.1 86.5
90 116.5 116.5 116.6 116.6 117.6 115.4 113.3 113.3 113.4 113.4 113.5 113.5 109.5 109.5 109.6 109.6 109.7 109.7 105.3 105.3 105.4 105.4 105.5 105.5
75 99.3 99.3 106.0 75.9 115.1 45.5 96.6 96.6 102.6 74.5 110.7 44.1 93.2 93.2 98.5 72.7 106.1 42.6 89.3 89.3 93.9 70.7 100.8 41.0
6000 80 105.6 105.6 107.0 101.4 116.6 71.8 102.6 102.6 103.7 100.0 112.5 70.5 99.1 99.1 99.8 98.3 107.9 69.1 95.1 95.1 95.1 95.1 103.0 67.5
85 112.0 112.0 112.1 112.1 117.2 95.5 108.9 108.9 109.0 109.0 113.3 94.0 105.2 105.2 105.2 105.2 108.8 92.3 101.0 101.0 101.0 101.0 103.9 90.5
90 118.5 118.5 118.6 118.6 118.7 118.7 115.2 115.2 115.3 115.3 115.4 115.4 111.4 111.4 111.5 111.5 111.5 111.5 107.0 107.0 107.1 107.1 107.2 107.2
Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-14 — Gross Cooling Capacities (kW) - Single Compressor - TTA155C Condensing Unit with TWE155B Air Handler (SI)
Ambient Temperature (°C)
29.4 35.0 40.6 46.1
Enter.
Dry Entering Wet Bulb (°C)
m
3
/h Bulb 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8
Airflow (°C) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
24 27.6 27.0 30.2 19.9 33.0 12.8 26.8 26.7 29.2 19.5 31.8 12.4 25.8 25.8 28.1 19.0 30.5 12.0 24.8 24.8 26.8 18.4 29.1 11.6
7646 27 29.1 29.1 30.3 25.7 33.2 18.5 28.4 28.4 29.4 25.3 32.1 18.1 27.4 27.4 28.3 24.8 30.8 17.6 26.3 26.3 27.0 24.3 29.4 17.1
29 30.8 30.8 30.9 30.9 33.4 24.3 30.0 30.0 30.1 30.1 32.3 23.9 29.1 29.1 29.1 29.1 31.1 23.4 27.9 27.9 28.0 28.0 29.7 22.9
32 32.6 32.6 32.6 32.6 33.6 30.2 31.7 31.7 31.8 31.8 32.6 29.8 30.7 30.7 30.7 30.7 31.3 29.4 29.6 29.6 29.6 29.6 30.0 28.9
24 28.0 28.0 30.5 21.1 33.3 12.9 27.3 27.3 29.6 20.7 32.1 12.5 26.4 26.4 28.4 20.3 30.8 12.0 25.3 25.3 27.1 19.2 29.3 11.6
8495 27 29.8 29.8 30.7 27.1 33.6 19.5 29.0 29.0 29.8 26.7 32.5 19.1 28.0 28.0 28.6 26.2 31.2 18.7 26.9 26.9 27.3 25.7 29.8 18.2
29 31.6 31.6 31.6 31.6 33.8 25.6 30.7 30.7 30.8 30.8 32.7 25.2 29.7 29.7 29.7 29.7 31.4 24.7 28.6 28.6 28.6 28.6 30.0 24.2
32 33.4 33.4 33.5 33.5 34.0 32.0 32.5 32.5 32.5 32.5 33.0 31.6 31.4 31.4 31.5 31.5 31.7 31.2 30.2 30.2 30.3 30.3 30.3 30.3
24 28.6 28.6 30.8 21.5 33.5 13.1 27.8 27.8 29.8 21.1 32.3 12.7 26.9 26.9 28.6 20.6 30.9 12.3 25.8 25.8 27.3 20.0 29.4 11.8
9345 27 30.4 30.4 31.0 28.4 33.9 20.3 29.6 29.6 30.1 28.0 32.7 19.9 28.6 28.6 28.9 27.5 31.4 19.5 27.4 27.4 27.6 27.0 30.0 19.0
29 32.2 32.2 32.3 32.3 34.1 26.8 31.3 31.3 31.4 31.4 32.9 26.4 30.3 30.3 30.3 30.3 31.6 25.9 29.1 29.1 29.1 29.1 30.2 25.3
32 34.1 34.1 34.1 34.1 34.4 33.8 33.2 33.2 33.2 33.2 33.2 33.2 32.1 32.1 32.1 32.1 32.1 32.1 30.8 30.8 30.9 30.9 30.9 30.9
24 29.1 29.1 31.0 22.2 33.7 13.3 28.3 28.3 30.0 21.8 32.4 12.9 27.3 27.3 28.8 21.3 31.1 12.5 26.1 26.1 27.5 20.7 29.5 12.0
10194 27 30.9 30.9 31.3 29.7 34.1 21.0 30.1 30.1 30.4 29.3 32.9 20.6 29.0 29.0 29.2 28.8 31.6 20.2 27.8 27.8 27.9 27.9 30.1 19.8
29 32.8 32.8 32.8 32.8 34.3 28.0 31.9 31.9 31.9 31.9 33.2 27.5 30.8 30.8 30.8 30.8 31.9 27.0 29.6 29.6 29.6 29.6 30.4 26.5
32 34.7 34.7 34.7 34.7 34.7 34.7 33.7 33.7 33.8 33.8 33.8 33.8 32.6 32.6 32.6 32.6 32.7 32.7 31.3 31.3 31.4 31.4 31.4 31.4
Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity