Trane TTA075A-TTA200B Air Conditioner User Manual


 
23SS-PRC003-EN
Performance
Data System
Table PD-10 — Gross Cooling Capacities (MBh) TTA125B Condensing Unit with TWE155B Air Handler (I-P)
Ambient Temperature (°F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (°F)
CFMBulb616773 61 6773616773616773
Airflow (°F) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
75 124.0 98.6 136.6 82.4 149.8 55.6 119.5 96.3 131.6 80.4 144.1 53.6 114.6 93.8 126.1 78.2 137.9 51.5 109.3 91.2 120.3 75.9 131.3 49.3
3750 80 124.7 115.3 136.9 94.8 150.4 73.4 120.2 113.0 131.9 92.5 144.8 71.3 115.5 110.6 126.5 90.1 138.9 69.1 110.5 108.1 120.8 87.5 132.5 66.8
85 128.0 128.0 137.5 111.4 151.0 90.7 124.2 124.2 132.5 109.1 145.4 88.7 120.1 120.1 127.1 106.7 139.5 86.5 115.6 115.6 121.4 104.1 132.8 83.5
90 134.5 134.5 138.2 128.2 151.2 107.1 130.6 130.6 133.3 125.9 145.7 104.9 126.3 126.3 128.2 123.6 139.9 102.5 121.7 121.7 122.8 121.1 133.6 100.0
75 126.6 103.5 139.2 81.3 152.2 56.6 121.9 101.2 134.0 79.1 146.3 54.6 116.9 98.7 128.4 76.8 140.0 52.4 111.4 96.0 121.9 73.8 133.2 50.2
4200 80 127.6 122.0 139.6 99.3 153.0 76.1 123.1 119.7 134.4 97.0 147.3 74.0 118.3 117.3 128.8 94.5 141.2 71.8 113.1 113.1 122.9 91.8 134.6 69.4
85 132.5 132.5 140.2 117.6 153.7 95.2 128.5 128.5 135.0 115.3 147.6 92.4 124.1 124.1 129.5 112.8 141.5 90.0 119.4 119.4 123.6 110.2 135.0 87.4
90 139.3 139.3 141.3 136.2 154.0 112.9 135.1 135.1 136.4 133.9 148.3 110.6 130.6 130.6 130.7 130.7 142.2 108.2 125.8 125.8 125.9 125.9 135.8 105.6
75 128.8 108.2 141.4 84.2 154.2 57.7 123.9 105.8 136.0 82.1 148.1 55.6 118.7 103.3 129.7 79.0 141.6 53.4 113.1 100.5 123.6 76.3 134.6 51.0
4650 80 130.2 128.5 141.8 103.6 155.2 78.7 125.3 125.3 136.5 101.2 149.3 76.5 120.9 120.9 130.8 98.7 143.0 74.3 116.1 116.1 124.7 96.0 136.2 71.9
85 136.4 136.4 142.4 123.5 155.6 98.5 132.2 132.2 137.2 121.2 149.7 96.2 127.5 127.5 131.5 118.6 143.5 93.7 122.6 122.6 125.6 116.0 136.9 91.1
90 143.4 143.4 144.2 144.0 156.3 118.4 139.0 139.0 139.2 139.2 150.4 116.1 134.3 134.3 134.4 134.4 144.2 113.6 129.2 129.2 129.3 129.3 137.6 111.0
75 130.6 112.7 142.7 86.5 155.8 58.6 125.6 110.3 137.3 84.1 149.6 56.4 120.3 107.7 131.3 81.4 142.9 54.1 114.7 104.9 125.1 78.6 135.8 51.7
5100 80 132.5 132.5 143.7 107.7 157.0 81.1 128.3 128.3 138.3 105.3 151.0 79.0 123.7 123.7 132.4 102.7 144.5 76.7 118.8 118.8 126.2 100.0 137.6 74.4
85 139.7 139.7 144.4 129.2 157.5 102.2 135.4 135.4 139.1 126.9 151.5 99.9 130.6 130.6 133.3 124.3 145.2 97.3 125.5 125.5 127.3 121.7 138.4 94.7
90 147.0 147.0 147.2 147.2 158.2 123.7 142.5 142.5 142.6 142.6 152.2 121.3 137.6 137.6 137.7 137.7 145.9 118.8 132.3 132.3 132.4 132.4 139.1 116.2
Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-10 — Gross Cooling Capacities (kW) TTA125B Condensing Unit with TWE155B Air Handler (SI)
Ambient Temperature (°C)
29.4 35.0 40.6 46.1
Enter.
Dry Entering Wet Bulb (°C)
m
3
/h Bulb 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8
Airflow (°C) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
24 36.3 28.9 40.0 24.1 43.9 16.3 35.0 28.2 38.5 23.5 42.2 15.7 33.6 27.5 36.9 22.9 40.4 15.1 32.0 26.7 35.2 22.2 38.5 14.4
6371 27 36.5 33.8 40.1 27.8 44.0 21.5 35.2 33.1 38.6 27.1 42.4 20.9 33.8 32.4 37.0 26.4 40.7 20.2 32.4 31.6 35.4 25.6 38.8 19.6
29 37.5 37.5 40.3 32.6 44.2 26.6 36.4 36.4 38.8 32.0 42.6 26.0 35.2 35.2 37.2 31.2 40.9 25.3 33.8 33.8 35.5 30.5 38.9 24.4
32 39.4 39.4 40.5 37.5 44.3 31.4 38.2 38.2 39.0 36.9 42.7 30.7 37.0 37.0 37.5 36.2 40.9 30.0 35.6 35.6 35.9 35.5 39.1 29.3
24 37.1 30.3 40.8 23.8 44.6 16.6 35.7 29.6 39.2 23.2 42.8 16.0 34.2 28.9 37.6 22.5 41.0 15.4 32.6 28.1 35.7 21.6 39.0 14.7
7136 27 37.4 35.7 40.9 29.1 44.8 22.3 36.0 35.1 39.4 28.4 43.1 21.7 34.6 34.3 37.7 27.7 41.3 21.0 33.1 33.1 36.0 26.9 39.4 20.3
29 38.8 38.8 41.0 34.4 45.0 27.9 37.6 37.6 39.5 33.7 43.2 27.1 36.3 36.3 37.9 33.0 41.4 26.3 35.0 35.0 36.2 32.3 39.5 25.6
32 40.8 40.8 41.4 39.9 45.1 33.1 39.6 39.6 39.9 39.2 43.4 32.4 38.2 38.2 38.3 38.3 41.7 31.7 36.8 36.8 36.9 36.9 39.8 30.9
24 37.7 31.7 41.4 24.7 45.1 16.9 36.3 31.0 39.8 24.0 43.4 16.3 34.8 30.2 38.0 23.1 41.5 15.6 33.1 29.4 36.2 22.3 39.4 14.9
7900 27 38.1 37.6 41.5 30.3 45.4 23.0 36.7 36.7 40.0 29.6 43.7 22.4 35.4 35.4 38.3 28.9 41.9 21.8 34.0 34.0 36.5 28.1 39.9 21.1
29 39.9 39.9 41.7 36.2 45.6 28.9 38.7 38.7 40.2 35.5 43.8 28.2 37.3 37.3 38.5 34.7 42.0 27.4 35.9 35.9 36.8 34.0 40.1 26.7
32 42.0 42.0 42.2 42.2 45.8 34.7 40.7 40.7 40.7 40.7 44.1 34.0 39.3 39.3 39.4 39.4 42.2 33.3 37.8 37.8 37.9 37.9 40.3 32.5
24 38.2 33.0 41.8 25.3 45.6 17.2 36.8 32.3 40.2 24.6 43.8 16.5 35.2 31.5 38.5 23.8 41.8 15.8 33.6 30.7 36.6 23.0 39.8 15.1
8665 27 38.8 38.8 42.1 31.5 46.0 23.8 37.6 37.6 40.5 30.8 44.2 23.1 36.2 36.2 38.8 30.1 42.3 22.5 34.8 34.8 37.0 29.3 40.3 21.8
29 40.9 40.9 42.3 37.8 46.1 29.9 39.6 39.6 40.7 37.1 44.4 29.2 38.2 38.2 39.0 36.4 42.5 28.5 36.7 36.7 37.3 35.6 40.5 27.7
32 43.0 43.0 43.1 43.1 46.3 36.2 41.7 41.7 41.8 41.8 44.6 35.5 40.3 40.3 40.3 40.3 42.7 34.8 38.7 38.7 38.8 38.8 40.7 34.0
Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity