16 SS-PRC003-EN
Performance
Data System
Table PD-3 — Gross Cooling Capacities (kW) TTA085A Condensing Unit with TWE075A Air Handler (SI)
Ambient Temperature (°C)
29.4 35.0 40.6 46.1
Enter.
Dry Entering Wet Bulb (°C)
m
3
/h Bulb 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8
Airflow (°C) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
24 24.2 18.5 26.8 15.6 29.8 10.9 23.3 18.0 25.9 15.2 28.7 10.5 22.4 17.6 24.9 14.8 27.6 10.1 21.5 17.1 23.9 14.4 26.5 9.7
3823 27 24.2 21.3 26.9 17.9 29.8 14.1 23.4 20.9 26.0 17.4 28.7 13.7 22.5 20.5 25.0 17.0 27.7 13.3 21.6 20.0 24.0 16.6 26.5 12.8
29 24.6 24.4 27.0 20.8 29.9 17.1 23.7 23.7 26.0 20.3 28.8 16.7 23.0 23.0 25.0 19.9 27.7 16.3 22.2 22.2 24.0 19.4 26.6 15.9
32 25.7 25.7 27.0 23.7 29.9 20.1 25.0 25.0 26.1 23.2 28.9 19.7 24.2 24.2 25.2 22.8 27.8 19.3 23.4 23.4 24.2 22.3 26.7 18.8
24 24.7 19.3 27.4 15.4 30.3 11.1 23.8 18.8 26.4 15.0 29.3 10.7 22.9 18.4 25.4 14.5 28.1 10.3 21.9 17.9 24.3 14.1 26.9 9.9
4248 27 24.8 22.5 27.5 18.7 30.4 14.5 24.0 22.0 26.5 18.3 29.3 14.1 23.1 21.6 25.4 17.7 28.2 13.7 22.1 21.1 24.4 17.3 27.0 13.3
29 25.3 25.3 27.5 21.8 30.5 17.8 24.6 24.6 26.6 21.4 29.4 17.4 23.8 23.8 25.6 20.9 28.3 17.0 23.0 23.0 24.5 20.4 27.1 16.6
32 26.6 26.6 27.7 25.0 30.5 21.1 25.9 25.9 26.7 24.6 29.4 20.6 25.1 25.1 25.8 24.1 28.3 20.2 24.3 24.3 24.8 23.7 27.2 19.7
24 25.2 20.1 27.9 15.9 30.8 11.3 24.3 19.6 26.9 15.5 29.7 10.9 23.3 19.2 25.8 15.0 28.5 10.5 22.3 18.7 24.7 14.6 27.3 10.1
4672 27 25.3 23.5 27.9 19.4 30.9 15.0 24.5 23.1 26.9 18.9 29.7 14.6 23.5 22.6 25.9 18.5 28.6 14.1 22.6 22.2 24.8 18.0 27.4 13.7
29 26.1 26.1 28.0 22.8 31.0 18.5 25.3 25.3 27.0 22.3 29.8 18.1 24.5 24.5 26.0 21.9 28.7 17.7 23.7 23.7 24.9 21.4 27.5 17.3
32 27.5 27.5 28.2 26.3 31.0 22.0 26.7 26.7 27.3 25.8 29.9 21.5 25.9 25.9 26.3 25.4 28.8 21.1 25.0 25.0 25.3 24.9 27.6 20.6
24 25.6 20.8 28.3 16.4 31.2 11.5 24.6 20.4 27.2 15.9 30.0 11.1 23.6 19.9 26.2 15.5 28.8 10.7 22.6 19.4 25.0 15.0 27.6 10.2
5097 27 25.8 24.6 28.3 20.1 31.3 15.4 24.9 24.1 27.3 19.6 30.1 15.0 24.0 23.7 26.2 19.1 28.9 14.5 22.9 22.9 25.1 18.6 27.7 14.1
29 26.8 26.8 28.5 23.7 31.4 19.2 26.0 26.0 27.4 23.3 30.2 18.8 25.1 25.1 26.4 22.8 29.1 18.4 24.3 24.3 25.3 22.3 27.8 17.8
32 28.2 28.2 28.7 27.5 31.4 22.8 27.4 27.4 27.8 27.0 30.3 22.4 26.5 26.5 26.8 26.6 29.1 21.9 25.6 25.6 25.7 25.7 27.9 21.5
Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-3 — Gross Cooling Capacities (MBh) TTA085A Condensing Unit with TWE075A Air Handler (I-P)
Ambient Temperature (°F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (°F)
CFMBulb616773 61 6773616773616773
Airflow (°F) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
75 82.5 63.0 91.6 53.2 101.7 37.2 79.6 61.5 88.4 51.9 98.1 35.9 76.5 60.0 85.0 50.5 94.3 34.6 73.3 58.3 81.5 49.1 90.4 33.2
2250 80 82.8 72.9 91.9 61.0 101.7 48.1 80.0 71.4 88.7 59.6 98.2 46.7 77.0 69.9 85.4 58.1 94.5 45.3 73.8 68.3 81.9 56.6 90.6 43.8
85 84.0 83.3 92.1 70.9 102.0 58.4 81.0 81.0 88.9 69.4 98.4 57.0 78.5 78.5 85.5 67.9 94.8 55.6 75.9 75.9 82.1 66.3 90.9 54.1
90 87.7 87.7 92.4 80.8 102.2 68.7 85.3 85.3 89.3 79.4 98.7 67.3 82.7 82.7 86.0 77.9 95.0 65.9 80.1 80.1 82.6 76.3 91.0 64.1
75 84.4 65.9 93.6 52.5 103.7 37.9 81.4 64.4 90.3 51.1 99.9 36.6 78.2 62.8 86.8 49.6 96.0 35.3 74.8 61.1 83.1 48.1 91.9 33.9
2500 80 84.8 76.7 93.9 63.8 103.7 49.6 81.9 75.2 90.6 62.3 100.0 48.2 78.8 73.7 86.9 60.6 96.2 46.8 75.6 72.1 83.3 59.0 92.2 45.3
85 86.4 86.4 94.1 74.4 104.0 60.9 83.9 83.9 90.8 72.9 100.4 59.5 81.3 81.3 87.3 71.4 96.5 58.1 78.6 78.6 83.7 69.8 92.6 56.6
90 90.9 90.9 94.5 85.3 104.3 72.1 88.4 88.4 91.3 83.9 100.4 70.4 85.7 85.7 88.0 82.4 96.7 68.9 82.9 82.9 84.5 80.8 92.7 67.3
75 85.9 68.6 95.2 54.2 105.2 38.7 82.8 67.0 91.8 52.8 101.4 37.3 79.5 65.4 88.2 51.3 97.3 36.0 76.1 63.7 84.4 49.8 93.1 34.5
2750 80 86.5 80.4 95.3 66.1 105.4 51.1 83.5 78.9 91.9 64.6 101.6 49.7 80.4 77.3 88.4 63.0 97.6 48.2 77.1 75.7 84.7 61.4 93.5 46.8
85 89.0 89.0 95.7 77.8 105.7 63.3 86.4 86.4 92.3 76.3 101.9 61.9 83.7 83.7 88.8 74.7 98.0 60.4 80.9 80.9 85.1 73.1 93.9 59.0
90 93.8 93.8 96.4 89.7 105.8 75.0 91.1 91.1 93.2 88.2 102.1 73.5 88.3 88.3 89.8 86.7 98.2 72.0 85.4 85.4 86.3 85.1 94.2 70.4
75 87.3 71.2 96.6 55.9 106.6 39.4 84.1 69.6 93.1 54.4 102.6 38.0 80.7 68.0 89.4 52.9 98.5 36.5 77.2 66.2 85.5 51.3 94.2 35.0
3000 80 88.1 83.9 96.8 68.5 106.8 52.5 85.1 82.4 93.3 67.0 102.9 51.1 81.9 80.8 89.6 65.3 98.9 49.6 78.3 78.3 85.8 63.7 94.7 48.1
85 91.4 91.4 97.2 81.0 107.2 65.6 88.7 88.7 93.7 79.5 103.3 64.2 85.9 85.9 90.1 77.9 99.3 62.7 82.9 82.9 86.3 76.3 94.9 60.8
90 96.3 96.3 98.2 93.9 107.3 78.0 93.5 93.5 94.9 92.4 103.5 76.5 90.6 90.6 91.4 90.8 99.5 74.9 87.6 87.6 87.6 87.6 95.4 73.3
Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity