Trane TTA075A-TTA200B Air Conditioner User Manual


 
18 SS-PRC003-EN
Table PD-5 — Gross Cooling Capacities (MBh) TTA100A Condensing Unit with TWE100A Air Handler (I-P)
Ambient Temperature (°F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (°F)
CFMBulb616773 61 6773616773616773
Airflow (°F) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
75 104.7 81.7 115.8 68.5 127.7 46.8 100.9 79.7 111.5 66.8 123.0 45.1 96.8 77.7 107.1 65.0 118.1 43.5 92.4 75.5 102.5 63.2 112.9 41.7
3025 80 105.2 95.0 116.1 78.6 127.8 61.1 101.5 93.1 111.9 76.8 123.2 59.3 97.5 91.1 107.5 75.0 118.3 57.5 93.3 89.0 102.9 73.0 113.3 55.6
85 106.9 106.9 116.3 92.0 128.1 74.9 103.8 103.8 112.1 90.1 123.5 73.1 100.4 100.4 107.7 88.1 118.7 71.3 96.9 96.9 103.1 86.1 113.7 69.5
90 112.3 112.3 116.8 105.4 128.4 88.7 109.1 109.1 112.7 103.5 123.8 86.9 105.7 105.7 108.4 101.6 119.0 85.1 102.1 102.1 104.1 99.7 113.8 82.9
75 106.8 85.3 118.0 67.1 129.8 47.6 102.8 83.3 113.6 65.3 124.9 46.0 98.6 81.2 109.0 63.4 119.8 44.2 94.2 79.1 104.3 61.5 114.5 42.4
3350 80 107.5 99.9 118.3 82.1 130.0 63.0 103.7 98.0 113.9 80.3 125.2 61.2 99.6 96.0 109.4 78.4 120.2 59.4 95.4 93.9 104.5 76.0 115.0 57.5
85 110.4 110.4 118.4 96.5 130.3 78.1 107.1 107.1 114.1 94.6 125.5 76.3 103.7 103.7 109.6 92.6 120.6 74.5 100.0 100.0 104.9 90.5 115.4 72.6
90 116.1 116.1 119.2 111.2 130.5 93.1 112.7 112.7 115.0 109.3 125.6 90.9 109.1 109.1 110.7 107.4 120.7 89.0 105.4 105.4 106.3 105.4 115.6 87.0
75 108.6 88.8 119.7 69.3 131.5 48.5 104.5 86.8 115.2 67.4 126.5 46.8 100.2 84.7 110.6 65.5 121.2 44.9 95.6 82.4 105.7 63.5 115.8 43.0
3675 80 109.5 104.7 120.1 85.4 131.7 64.8 105.6 102.7 115.4 83.2 126.8 63.1 101.6 100.7 110.8 81.2 121.7 61.2 97.0 97.0 105.9 79.1 116.4 59.3
85 113.5 113.5 120.3 100.8 132.1 81.1 110.1 110.1 115.8 98.8 127.2 79.3 106.4 106.4 111.2 96.8 122.1 77.5 102.6 102.6 106.5 94.8 116.8 75.6
90 119.4 119.4 121.4 116.8 132.2 96.8 115.8 115.8 117.2 114.9 127.3 94.9 112.1 112.1 112.2 112.2 122.3 92.9 108.2 108.2 108.3 108.3 117.0 90.9
75 110.1 92.1 121.2 71.3 132.9 49.2 105.9 90.0 116.6 69.4 127.8 47.4 101.5 87.9 111.9 67.5 122.4 45.5 96.9 85.7 106.9 65.6 116.8 43.6
4000 80 111.4 109.2 121.4 88.2 133.2 66.6 107.5 107.3 116.9 86.2 128.2 64.8 103.1 103.1 112.1 84.2 123.0 63.0 99.3 99.3 107.2 82.0 117.6 61.1
85 116.3 116.3 121.9 105.0 133.6 84.0 112.7 112.7 117.4 103.0 128.6 82.2 108.9 108.9 112.7 101.0 123.4 80.4 105.0 105.0 107.9 98.9 117.8 78.0
90 122.3 122.3 123.5 122.3 133.8 100.7 118.6 118.6 118.7 118.7 128.8 98.7 114.7 114.7 114.8 114.8 123.7 96.8 110.7 110.7 110.8 110.8 118.3 94.7
Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-5 — Gross Cooling Capacities (kW) TTA100A Condensing Unit with TWE100A Air Handler (SI)
Ambient Temperature (°C)
29.4 35.0 40.6 46.1
Enter.
Dry Entering Wet Bulb (°C)
m
3
/h Bulb 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8
Airflow (°C) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
24 30.7 23.9 33.9 20.1 37.4 13.7 29.5 23.3 32.7 19.6 36.0 13.2 28.3 22.7 31.4 19.0 34.6 12.7 27.1 22.1 30.0 18.5 33.1 12.2
5139 27 30.8 27.8 34.0 23.0 37.4 17.9 29.7 27.3 32.8 22.5 36.1 17.4 28.5 26.7 31.5 22.0 34.6 16.8 27.3 26.1 30.1 21.4 33.2 16.3
29 31.3 31.3 34.0 26.9 37.5 21.9 30.4 30.4 32.8 26.4 36.2 21.4 29.4 29.4 31.5 25.8 34.7 20.9 28.4 28.4 30.2 25.2 33.3 20.3
32 32.9 32.9 34.2 30.9 37.6 26.0 31.9 31.9 33.0 30.3 36.2 25.5 30.9 30.9 31.8 29.8 34.8 24.9 29.9 29.9 30.5 29.2 33.3 24.3
24 31.3 25.0 34.5 19.7 38.0 13.9 30.1 24.4 33.3 19.1 36.6 13.5 28.9 23.8 31.9 18.6 35.1 12.9 27.6 23.1 30.5 18.0 33.5 12.4
5692 27 31.5 29.3 34.6 24.0 38.1 18.5 30.3 28.7 33.4 23.5 36.7 17.9 29.2 28.1 32.0 23.0 35.2 17.4 27.9 27.5 30.6 22.3 33.7 16.8
29 32.3 32.3 34.7 28.3 38.1 22.9 31.4 31.4 33.4 27.7 36.8 22.3 30.3 30.3 32.1 27.1 35.3 21.8 29.3 29.3 30.7 26.5 33.8 21.3
32 34.0 34.0 34.9 32.6 38.2 27.2 33.0 33.0 33.7 32.0 36.8 26.6 31.9 31.9 32.4 31.4 35.3 26.1 30.9 30.9 31.1 30.9 33.8 25.5
24 31.8 26.0 35.1 20.3 38.5 14.2 30.6 25.4 33.7 19.7 37.0 13.7 29.3 24.8 32.4 19.2 35.5 13.2 28.0 24.1 30.9 18.6 33.9 12.6
6244 27 32.1 30.6 35.2 25.0 38.6 19.0 30.9 30.1 33.8 24.4 37.1 18.5 29.7 29.5 32.4 23.8 35.6 17.9 28.4 28.4 31.0 23.2 34.1 17.4
29 33.2 33.2 35.2 29.5 38.7 23.7 32.2 32.2 33.9 28.9 37.2 23.2 31.2 31.2 32.6 28.4 35.8 22.7 30.0 30.0 31.2 27.8 34.2 22.1
32 35.0 35.0 35.6 34.2 38.7 28.3 33.9 33.9 34.3 33.7 37.3 27.8 32.8 32.8 32.8 32.8 35.8 27.2 31.7 31.7 31.7 31.7 34.3 26.6
24 32.2 27.0 35.5 20.9 38.9 14.4 31.0 26.4 34.2 20.3 37.4 13.9 29.7 25.7 32.8 19.8 35.8 13.3 28.4 25.1 31.3 19.2 34.2 12.8
6796 27 32.6 32.0 35.6 25.8 39.0 19.5 31.5 31.4 34.2 25.2 37.5 19.0 30.2 30.2 32.8 24.6 36.0 18.4 29.1 29.1 31.4 24.0 34.4 17.9
29 34.0 34.0 35.7 30.7 39.1 24.6 33.0 33.0 34.4 30.2 37.7 24.1 31.9 31.9 33.0 29.6 36.1 23.5 30.7 30.7 31.6 29.0 34.5 22.8
32 35.8 35.8 36.2 35.8 39.2 29.5 34.7 34.7 34.8 34.8 37.7 28.9 33.6 33.6 33.6 33.6 36.2 28.3 32.4 32.4 32.4 32.4 34.6 27.7
Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Performance
Data System