Trane TTA075A-TTA200B Air Conditioner User Manual


 
17SS-PRC003-EN
Performance
Data System
Table PD-4 — Gross Cooling Capacities (MBh) TTA085A Condensing Unit with TWE100A Air Handler (I-P)
Ambient Temperature (°F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (°F)
CFMBulb616773 61 6773616773616773
Airflow (°F) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
75 87.7 68.7 97.0 57.2 107.1 39.2 84.5 67.1 93.5 55.8 103.1 37.9 81.1 65.4 89.8 54.3 98.9 36.4 77.6 63.7 86.0 52.7 94.6 35.0
2500 80 88.0 80.1 97.3 66.3 107.2 51.4 84.9 78.5 93.8 64.8 103.4 49.9 81.6 76.9 90.1 63.2 99.3 48.4 78.2 75.1 86.1 61.3 95.1 46.9
85 89.8 89.8 97.5 77.6 107.6 63.2 87.2 87.2 94.0 76.0 103.7 61.7 84.4 84.4 90.3 74.3 99.7 60.2 81.5 81.5 86.5 72.7 95.5 58.7
90 94.4 94.4 97.9 89.0 107.8 74.9 91.7 91.7 94.4 87.4 103.9 73.5 88.9 88.9 90.9 85.8 99.8 71.6 85.9 85.9 87.3 84.2 95.6 70.0
75 89.6 72.2 99.1 56.7 109.0 40.0 86.3 70.6 95.4 55.2 104.9 38.6 82.8 68.9 91.6 53.6 100.5 37.2 79.2 67.1 87.6 52.0 96.0 35.6
2800 80 90.2 84.8 99.4 69.7 109.3 53.3 87.0 83.2 95.5 67.8 105.3 51.8 83.7 81.6 91.7 66.2 101.1 50.3 80.2 79.9 87.8 64.4 96.7 48.7
85 93.1 93.1 99.5 81.9 109.6 66.3 90.4 90.4 95.9 80.3 105.6 64.8 87.4 87.4 92.1 78.6 101.5 63.3 84.4 84.4 88.2 76.9 97.1 61.7
90 98.0 98.0 100.2 94.6 109.7 78.8 95.1 95.1 96.7 93.0 105.7 77.2 92.1 92.1 93.1 91.4 101.6 75.6 89.0 89.0 89.1 89.1 97.3 73.9
75 91.2 75.5 100.7 58.8 110.5 40.8 87.8 73.9 96.9 57.3 106.2 39.4 84.2 72.1 93.0 55.7 101.8 37.9 80.5 70.3 88.9 54.1 97.2 36.3
3100 80 92.1 89.4 100.9 72.5 111.0 55.1 88.9 87.8 97.1 70.8 106.8 53.6 85.2 85.2 93.2 69.1 102.5 52.1 82.1 82.1 89.2 67.4 98.1 50.5
85 96.1 96.1 101.2 86.1 111.3 69.2 93.1 93.1 97.5 84.5 107.2 67.7 90.1 90.1 93.7 82.8 102.9 66.2 86.9 86.9 89.7 81.1 98.3 64.1
90 101.1 101.1 102.3 100.0 111.5 82.7 98.1 98.1 98.8 98.5 107.4 81.1 94.9 94.9 95.0 95.0 103.1 79.5 91.6 91.6 91.7 91.7 98.7 77.8
75 92.6 78.7 102.1 60.8 111.8 41.5 89.1 77.0 98.2 59.2 107.4 40.0 85.5 75.3 94.2 57.6 102.9 38.4 81.7 73.5 90.0 56.0 98.2 36.8
3400 80 93.9 93.8 102.3 75.4 112.4 56.8 90.5 90.5 98.5 73.7 108.1 55.3 87.4 87.4 94.5 72.0 103.7 53.8 84.1 84.1 90.3 70.2 99.2 52.2
85 98.6 98.6 102.7 90.1 112.8 72.0 95.6 95.6 99.0 88.5 108.3 70.1 92.4 92.4 95.0 86.8 104.0 68.5 89.0 89.0 91.0 85.1 99.4 66.7
90 103.8 103.8 103.9 103.9 112.9 86.4 100.7 100.7 100.8 100.8 108.7 84.8 97.4 97.4 97.5 97.5 104.4 83.2 94.0 94.0 94.0 94.0 99.9 81.4
Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-4 — Gross Cooling Capacities (kW) TTA085A Condensing Unit with TWE100A Air Handler (SI)
Ambient Temperature (°C)
29.4 35.0 40.6 46.1
Enter.
Dry Entering Wet Bulb (°C)
m
3
/h Bulb 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8
Airflow (°C) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
24 25.7 20.1 28.4 16.7 31.4 11.5 24.7 19.6 27.4 16.3 30.2 11.1 23.7 19.2 26.3 15.9 29.0 10.7 22.7 18.6 25.2 15.4 27.7 10.2
4248 27 25.8 23.4 28.5 19.4 31.4 15.1 24.9 23.0 27.5 19.0 30.3 14.6 23.9 22.5 26.4 18.5 29.1 14.2 22.9 22.0 25.2 18.0 27.9 13.7
29 26.3 26.3 28.5 22.7 31.5 18.5 25.5 25.5 27.5 22.2 30.4 18.1 24.7 24.7 26.4 21.8 29.2 17.6 23.9 23.9 25.3 21.3 28.0 17.2
32 27.6 27.6 28.7 26.1 31.6 21.9 26.8 26.8 27.7 25.6 30.4 21.5 26.0 26.0 26.6 25.1 29.2 21.0 25.1 25.1 25.6 24.7 28.0 20.5
24 26.2 21.1 29.0 16.6 31.9 11.7 25.3 20.7 27.9 16.2 30.7 11.3 24.2 20.2 26.8 15.7 29.4 10.9 23.2 19.6 25.6 15.2 28.1 10.4
4757 27 26.4 24.8 29.1 20.4 32.0 15.6 25.5 24.4 28.0 19.9 30.8 15.2 24.5 23.9 26.9 19.4 29.6 14.7 23.5 23.4 25.7 18.9 28.3 14.3
29 27.3 27.3 29.1 24.0 32.1 19.4 26.5 26.5 28.1 23.5 30.9 19.0 25.6 25.6 27.0 23.0 29.7 18.5 24.7 24.7 25.8 22.5 28.4 18.1
32 28.7 28.7 29.3 27.7 32.1 23.1 27.9 27.9 28.3 27.2 31.0 22.6 27.0 27.0 27.3 26.8 29.8 22.1 26.1 26.1 26.1 26.1 28.5 21.7
24 26.7 22.1 29.5 17.2 32.4 12.0 25.7 21.6 28.4 16.8 31.1 11.5 24.7 21.1 27.2 16.3 29.8 11.1 23.6 20.6 26.0 15.8 28.5 10.6
5267 27 27.0 26.2 29.5 21.2 32.5 16.1 26.0 25.7 28.4 20.7 31.3 15.7 25.0 25.0 27.3 20.2 30.0 15.2 24.0 24.0 26.1 19.7 28.7 14.8
29 28.1 28.1 29.6 25.2 32.6 20.3 27.3 27.3 28.5 24.7 31.4 19.8 26.4 26.4 27.4 24.2 30.1 19.4 25.4 25.4 26.3 23.7 28.8 18.8
32 29.6 29.6 30.0 29.3 32.6 24.2 28.7 28.7 28.9 28.8 31.4 23.7 27.8 27.8 27.8 27.8 30.2 23.3 26.8 26.8 26.9 26.9 28.9 22.8
24 27.1 23.1 29.9 17.8 32.7 12.1 26.1 22.6 28.8 17.3 31.5 11.7 25.0 22.0 27.6 16.9 30.1 11.2 23.9 21.5 26.4 16.4 28.8 10.8
5777 27 27.5 27.5 30.0 22.1 32.9 16.6 26.5 26.5 28.8 21.6 31.7 16.2 25.6 25.6 27.7 21.1 30.4 15.7 24.6 24.6 26.4 20.6 29.0 15.3
29 28.9 28.9 30.1 26.4 33.0 21.1 28.0 28.0 29.0 25.9 31.7 20.5 27.0 27.0 27.8 25.4 30.4 20.0 26.1 26.1 26.6 24.9 29.1 19.5
32 30.4 30.4 30.4 30.4 33.1 25.3 29.5 29.5 29.5 29.5 31.8 24.8 28.5 28.5 28.6 28.6 30.6 24.4 27.5 27.5 27.5 27.5 29.2 23.8
Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity