Trane TTA075A-TTA200B Air Conditioner User Manual


 
24 SS-PRC003-EN
Performance
Data System
Table PD-11 — Gross Cooling Capacities (MBh) TTA155B Condensing Unit with TWE155B Air Handler (I-P)
Ambient Temperature (°F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (°F)
CFMBulb616773 61 6773616773616773
Airflow (°F) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
75 153.4 120.3 169.3 101.1 185.9 68.9 148.2 117.6 163.3 98.6 178.9 66.4 142.0 114.4 156.3 95.8 170.9 63.7 134.9 110.8 148.4 92.6 162.0 60.6
4500 80 154.3 140.1 169.6 116.0 186.6 90.3 149.1 137.4 163.7 113.2 179.8 87.7 143.0 134.3 156.7 110.0 172.0 84.8 136.2 130.8 149.0 106.4 163.5 81.7
85 157.3 157.3 170.5 135.7 187.4 111.0 152.9 152.9 164.5 132.9 180.6 108.4 147.7 147.7 157.6 129.7 172.9 105.5 141.7 141.7 149.9 126.2 163.9 101.7
90 165.4 165.4 171.3 155.6 187.6 130.6 160.8 160.8 165.5 152.8 180.9 127.9 155.3 155.3 158.8 149.7 173.3 124.7 149.2 149.2 151.4 146.3 165.0 121.3
75 156.6 125.7 172.5 99.4 188.8 70.0 151.1 122.9 166.2 96.8 181.5 67.5 144.6 119.7 158.9 93.8 173.3 64.7 137.3 116.0 150.8 90.5 164.2 61.6
5000 80 157.7 147.5 172.9 120.9 189.8 93.3 152.4 144.8 166.7 118.1 182.7 90.7 146.1 141.6 159.5 114.8 174.7 87.7 139.2 138.0 151.6 111.2 166.0 84.6
85 162.6 162.6 173.8 142.5 190.6 115.9 157.9 157.9 167.6 139.6 183.6 113.3 152.4 152.4 160.4 136.4 175.2 109.4 146.1 146.1 152.5 132.8 166.5 105.9
90 171.0 171.0 175.0 164.3 191.1 137.0 166.1 166.1 169.0 161.6 184.1 134.1 160.3 160.3 162.2 158.4 176.2 130.9 153.9 153.9 154.0 154.0 167.6 127.4
75 159.3 130.9 175.1 102.7 191.1 71.3 153.6 128.1 168.6 100.0 183.6 68.7 146.9 124.7 161.1 97.0 175.2 65.9 139.4 120.9 152.2 92.7 165.9 62.6
5500 80 160.8 154.6 175.7 125.6 192.4 96.1 155.3 151.8 169.2 122.7 185.1 93.5 149.0 148.6 161.9 119.4 176.9 90.5 141.9 141.9 153.7 115.7 167.9 87.3
85 167.2 167.2 176.5 148.9 192.8 119.7 162.3 162.3 170.1 146.0 185.6 116.8 156.5 156.5 162.8 142.7 177.5 113.6 149.9 149.9 154.7 139.1 168.7 110.0
90 175.9 175.9 178.3 172.8 194.0 143.0 170.7 170.7 172.2 170.0 186.7 140.1 164.7 164.7 164.8 164.8 178.6 136.8 157.9 157.9 158.1 158.1 169.8 133.3
75 161.5 135.9 177.3 105.9 193.1 72.5 155.6 132.9 170.6 103.2 185.5 69.7 148.8 129.5 162.4 99.0 176.8 66.7 141.2 125.7 154.0 95.3 167.3 63.5
6000 80 163.6 161.5 178.0 130.1 194.7 98.8 157.4 157.4 171.4 127.2 187.2 96.1 151.6 151.6 163.8 123.8 178.8 93.2 145.0 145.0 155.5 120.0 169.6 90.0
85 171.3 171.3 178.9 155.2 195.3 123.8 166.1 166.1 172.4 152.3 187.8 120.8 160.0 160.0 164.9 148.9 179.6 117.5 153.2 153.2 156.8 145.3 170.6 113.9
90 180.2 180.2 181.4 181.0 196.5 148.8 174.7 174.7 174.9 174.9 188.8 145.8 168.5 168.5 168.6 168.6 180.7 142.5 161.5 161.5 161.6 161.6 171.7 139.0
Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-11 — Gross Cooling Capacities (kW) TTA155B Condensing Unit with TWE155B Air Handler (SI)
Ambient Temperature (°C)
29.4 35.0 40.6 46.1
Enter.
Dry Entering Wet Bulb (°C)
m
3
/h Bulb 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8
Airflow (°C) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
24 44.9 35.2 49.6 29.6 54.4 20.2 43.4 34.4 47.8 28.9 52.4 19.4 41.6 33.5 45.8 28.0 50.0 18.6 39.5 32.4 43.5 27.1 47.4 17.8
7646 27 45.2 41.0 49.7 34.0 54.6 26.4 43.7 40.2 47.9 33.1 52.6 25.7 41.9 39.3 45.9 32.2 50.4 24.8 39.9 38.3 43.6 31.2 47.9 23.9
29 46.1 46.1 49.9 39.7 54.9 32.5 44.8 44.8 48.2 38.9 52.9 31.7 43.2 43.2 46.2 38.0 50.6 30.9 41.5 41.5 43.9 36.9 48.0 29.8
32 48.4 48.4 50.2 45.6 54.9 38.3 47.1 47.1 48.5 44.8 53.0 37.4 45.5 45.5 46.5 43.8 50.8 36.5 43.7 43.7 44.3 42.8 48.3 35.5
8495 24 45.8 36.8 50.5 29.1 55.3 20.5 44.2 36.0 48.7 28.3 53.1 19.8 42.4 35.0 46.5 27.5 50.7 18.9 40.2 34.0 44.2 26.5 48.1 18.0
27 46.2 43.2 50.6 35.4 55.6 27.3 44.6 42.4 48.8 34.6 53.5 26.5 42.8 41.5 46.7 33.6 51.2 25.7 40.8 40.4 44.4 32.6 48.6 24.8
29 47.6 47.6 50.9 41.7 55.8 33.9 46.2 46.2 49.1 40.9 53.8 33.2 44.6 44.6 47.0 39.9 51.3 32.0 42.8 42.8 44.6 38.9 48.8 31.0
32 50.1 50.1 51.2 48.1 56.0 40.1 48.6 48.6 49.5 47.3 53.9 39.3 46.9 46.9 47.5 46.4 51.6 38.3 45.1 45.1 45.1 45.1 49.1 37.3
9345 24 46.6 38.3 51.3 30.1 56.0 20.9 45.0 37.5 49.4 29.3 53.8 20.1 43.0 36.5 47.2 28.4 51.3 19.3 40.8 35.4 44.6 27.1 48.6 18.3
27 47.1 45.3 51.4 36.8 56.3 28.1 45.5 44.5 49.6 35.9 54.2 27.4 43.6 43.5 47.4 35.0 51.8 26.5 41.6 41.6 45.0 33.9 49.2 25.6
29 49.0 49.0 51.7 43.6 56.5 35.1 47.5 47.5 49.8 42.8 54.3 34.2 45.8 45.8 47.7 41.8 52.0 33.3 43.9 43.9 45.3 40.7 49.4 32.2
32 51.5 51.5 52.2 50.6 56.8 41.9 50.0 50.0 50.4 49.8 54.7 41.0 48.2 48.2 48.3 48.3 52.3 40.1 46.2 46.2 46.3 46.3 49.7 39.0
10194 24 47.3 39.8 51.9 31.0 56.5 21.2 45.6 38.9 50.0 30.2 54.3 20.4 43.6 37.9 47.5 29.0 51.8 19.5 41.3 36.8 45.1 27.9 49.0 18.6
27 47.9 47.3 52.1 38.1 57.0 28.9 46.1 46.1 50.2 37.2 54.8 28.2 44.4 44.4 48.0 36.2 52.3 27.3 42.5 42.5 45.5 35.1 49.7 26.3
29 50.2 50.2 52.4 45.4 57.2 36.3 48.6 48.6 50.5 44.6 55.0 35.4 46.9 46.9 48.3 43.6 52.6 34.4 44.9 44.9 45.9 42.5 50.0 33.4
32 52.8 52.8 53.1 53.0 57.5 43.6 51.2 51.2 51.2 51.2 55.3 42.7 49.3 49.3 49.4 49.4 52.9 41.7 47.3 47.3 47.3 47.3 50.3 40.7
Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity