Trane TTA075A-TTA200B Air Conditioner User Manual


 
25SS-PRC003-EN
Performance
Data System
Table PD-12— Gross Cooling Capacities (MBh) TTA155B Condensing Unit with TWE200B Air Handler (I-P)
Ambient Temperature (°F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (°F)
CFMBulb616773 61 6773616773616773
Airflow (°F) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
75 157.9 124.4 174.3 103.2 191.0 70.7 152.4 121.5 168.0 100.6 183.7 68.2 145.9 118.2 160.7 97.7 175.3 65.3 138.5 114.5 152.5 94.4 166.2 62.2
4500 80 158.8 145.1 174.6 119.9 192.0 93.1 153.4 142.3 168.4 117.0 184.9 90.5 147.0 139.1 161.1 113.7 176.9 87.5 139.9 135.4 153.1 110.0 168.1 84.2
85 162.4 162.4 175.4 140.4 192.8 114.7 157.7 157.7 169.2 137.6 185.8 112.0 152.2 152.2 162.0 134.3 177.8 109.1 146.0 146.0 154.0 130.6 168.5 105.0
90 170.7 170.7 176.3 161.3 193.0 135.2 165.8 165.8 170.2 158.4 186.1 132.3 160.1 160.1 163.3 155.2 178.2 129.1 153.7 153.7 155.6 151.7 169.6 125.6
75 161.2 130.3 177.6 102.7 193.9 71.9 155.4 127.3 171.0 100.0 186.4 69.3 148.7 123.9 163.4 96.9 177.8 66.4 141.0 120.1 155.0 93.5 168.4 63.2
5000 80 162.4 153.1 178.0 125.2 195.2 96.3 156.8 150.2 171.5 122.2 187.9 93.6 150.3 146.9 164.0 118.8 179.7 90.6 142.6 142.6 155.8 115.1 170.6 87.4
85 167.9 167.9 178.8 147.8 196.1 119.9 163.0 163.0 172.4 144.8 188.9 117.3 157.2 157.2 164.9 141.5 180.1 113.2 150.6 150.6 156.7 137.8 171.3 109.6
90 176.6 176.6 180.2 170.7 196.5 141.9 171.4 171.4 173.9 167.9 189.3 139.0 165.4 165.4 166.9 164.6 181.2 135.8 158.7 158.7 158.9 158.9 172.4 132.2
75 164.0 135.9 180.2 106.3 196.3 73.2 158.0 132.9 173.5 103.5 188.6 70.6 151.0 129.4 165.7 100.4 179.8 67.6 143.2 125.5 156.3 95.6 170.1 64.4
5500 80 165.6 160.8 180.8 130.2 197.9 99.4 159.9 157.9 174.1 127.2 190.4 96.7 153.0 153.0 166.5 123.8 182.0 93.6 146.3 146.3 158.0 120.0 172.7 90.4
85 172.8 172.8 181.7 154.8 198.4 124.0 167.6 167.6 175.0 151.8 190.9 121.0 161.5 161.5 167.5 148.4 182.6 117.6 154.7 154.7 159.1 144.7 173.6 114.0
90 181.7 181.7 183.6 179.9 199.4 148.4 176.3 176.3 177.4 177.0 192.0 145.5 170.0 170.0 170.2 170.2 183.7 142.2 163.0 163.0 163.2 163.2 174.7 138.6
75 166.3 141.2 182.5 109.7 198.4 74.4 160.2 138.2 174.9 105.9 190.4 71.7 153.0 134.6 167.0 102.3 181.4 68.6 145.1 130.7 158.8 100.2 171.5 65.3
6000 80 168.7 168.3 183.2 135.1 200.2 102.3 162.7 162.7 176.4 132.0 192.5 99.6 156.5 156.5 168.5 128.5 183.9 96.5 149.6 149.6 159.9 124.7 174.5 93.3
85 177.1 177.1 184.2 161.6 200.8 128.4 171.6 171.6 177.4 158.6 193.2 125.3 165.3 165.3 169.7 155.1 184.8 121.9 158.2 158.2 161.3 151.4 175.5 118.2
90 186.3 186.3 186.5 186.5 201.8 154.7 180.6 180.6 180.8 180.8 194.3 151.7 174.1 174.1 174.3 174.3 185.9 148.4 166.8 166.8 167.0 167.0 176.7 144.8
Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-12 — Gross Cooling Capacities (kW) TTA155B Condensing Unit with TWE200B Air Handler (SI)
Ambient Temperature (°C)
29.4 35.0 40.6 46.1
Enter.
Dry Entering Wet Bulb (°C)
m
3
/h Bulb 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8
Airflow (°C) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
23.9 46.2 36.4 51.0 30.2 55.9 20.7 44.6 35.6 49.2 29.5 53.8 20.0 42.7 34.6 47.0 28.6 51.3 19.1 40.5 33.5 44.6 27.6 48.7 18.2
7646 26.7 46.5 42.5 51.1 35.1 56.2 27.3 44.9 41.7 49.3 34.3 54.1 26.5 43.0 40.7 47.2 33.3 51.8 25.6 41.0 39.7 44.8 32.2 49.2 24.7
29.4 47.5 47.5 51.4 41.1 56.4 33.6 46.2 46.2 49.5 40.3 54.4 32.8 44.6 44.6 47.4 39.3 52.1 31.9 42.7 42.7 45.1 38.2 49.3 30.7
32.2 50.0 50.0 51.6 47.2 56.5 39.6 48.6 48.6 49.8 46.4 54.5 38.7 46.9 46.9 47.8 45.5 52.2 37.8 45.0 45.0 45.6 44.4 49.7 36.8
23.9 47.2 38.1 52.0 30.1 56.8 21.1 45.5 37.3 50.1 29.3 54.6 20.3 43.5 36.3 47.8 28.4 52.1 19.4 41.3 35.2 45.4 27.4 49.3 18.5
8495 26.7 47.6 44.8 52.1 36.6 57.2 28.2 45.9 44.0 50.2 35.8 55.0 27.4 44.0 43.0 48.0 34.8 52.6 26.5 41.7 41.7 45.6 33.7 50.0 25.6
29.4 49.2 49.2 52.4 43.3 57.4 35.1 47.7 47.7 50.5 42.4 55.3 34.3 46.0 46.0 48.3 41.4 52.7 33.1 44.1 44.1 45.9 40.3 50.1 32.1
32.2 51.7 51.7 52.7 50.0 57.5 41.6 50.2 50.2 50.9 49.2 55.4 40.7 48.4 48.4 48.9 48.2 53.1 39.8 46.5 46.5 46.5 46.5 50.5 38.7
23.9 48.0 39.8 52.8 31.1 57.5 21.4 46.3 38.9 50.8 30.3 55.2 20.7 44.2 37.9 48.5 29.4 52.6 19.8 41.9 36.7 45.8 28.0 49.8 18.8
9345 26.7 48.5 47.1 52.9 38.1 58.0 29.1 46.8 46.2 51.0 37.3 55.8 28.3 44.8 44.8 48.7 36.2 53.3 27.4 42.8 42.8 46.3 35.1 50.6 26.5
29.4 50.6 50.6 53.2 45.3 58.1 36.3 49.1 49.1 51.3 44.4 55.9 35.4 47.3 47.3 49.0 43.5 53.5 34.4 45.3 45.3 46.6 42.4 50.8 33.4
32.2 53.2 53.2 53.8 52.7 58.4 43.5 51.6 51.6 51.9 51.8 56.2 42.6 49.8 49.8 49.8 49.8 53.8 41.6 47.7 47.7 47.8 47.8 51.2 40.6
23.9 48.7 41.4 53.4 32.1 58.1 21.8 46.9 40.5 51.2 31.0 55.7 21.0 44.8 39.4 48.9 30.0 53.1 20.1 42.5 38.3 46.5 29.3 50.2 19.1
10194 26.7 49.4 49.3 53.7 39.6 58.6 30.0 47.6 47.6 51.6 38.7 56.4 29.1 45.8 45.8 49.4 37.6 53.8 28.3 43.8 43.8 46.8 36.5 51.1 27.3
29.4 51.8 51.8 53.9 47.3 58.8 37.6 50.3 50.3 52.0 46.4 56.6 36.7 48.4 48.4 49.7 45.4 54.1 35.7 46.3 46.3 47.2 44.3 51.4 34.6
32.2 54.5 54.5 54.6 54.6 59.1 45.3 52.9 52.9 52.9 52.9 56.9 44.4 51.0 51.0 51.0 51.0 54.4 43.5 48.8 48.8 48.9 48.9 51.7 42.4
Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.acity (SHC) is the total capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity