Trane TR200 Heating System User Manual


 
Input Conn. Term. Function Type
X57
1 Digital input for safety stop User supplied dry contact
2 Common User supplied dry contact
3Factory use only
4No function
5Factory use only
6Factory use only
7Factory use only
8 Digital input for remote bypass enable User supplied dry contact
9 Digital input overrides system to Bypass Mode ignoring all
other inputs and commands, except for safety stop on
terminal 1.
User supplied dry contact
10 Digital input for remote overload reset User supplied dry contact
Output Conn. Term. Function
X59
1 Common for binary I/O
2 Common for binary I/O
3No function
4No function
5 Digital output indicates panel is in Drive Mode. 24 VDC digital output
6 Digital output indicates panel is in Bypass Mode 24 VDC digital output
7 Common for binary I/O
8 Common for binary I/O
Relay Output Term. Function
X56
1 N.O. contact for running in bypass or drive Relay output for user
2 N.O. contact for running in bypass or drive Relay output for user
3-12 Factory use only
Table 6.2 ECB Card Terminals