Trane TR200 Heating System User Manual


 
3.1.3 Internal Main Panel Fuses
Use only the specified fuse or an equivalent replacement for the internal main fuses. See the specifications label inside the
cover of the unit for acceptable replacement main fuses. A sample of this can be seen in Table 3.6.
Fuse Description Manufacturer Part Number/Size
F13A & C Primary Transformer Bussmann FNQ-R-0.50
F15A, B, & C Main Fuses Bussmann LPJ-30-SP
F16A, B, & C Drive Fuses Bussmann JJS-35
F900, F901,F902 SMPS - Power Supply Bussmann FWH-020A6F, 500V
Table 3.6 Sample Fuse Rating Label
3.2 Mechanical Installation
3.2.1 Lifting
WARNING
Heavy Objects!
Do not use cables (chains or slings) except as shown. Each
of the cables (chains or slings) used to lift the unit must be
capable of supporting the entire weight of the unit. Lifting
cables (chains or slings) may not be of the same length.
Adjust as necessary for even unit lift. Other lifting
arrangements may cause equipment or property-only
damage. Failure to properly lift unit could result in death
or serious injury. See details below.
WARNING
Check the weight of unit to determine the safety of the
lifting method. Ensure that the lifting device is suitable for
the task. If necessary, plan for a hoist, crane or forklift with
appropriate rating to move the units.
Follow recommendations below. failure to do so could
result in death or serious injury.
3.2.2 Hoist or Overhead Lift
Use a solid steel spreader bar for lifting. Slide the
spreader bar through the two (2) lifting holes on
the panel. Lifting rings are 0.59in (15mm) in
diameter (see Figure 3.1). If VFD mounting screws
interfere with the spreader bar, lifting hooks can
be used instead of the lifting bar.
Connect the spreader bar to a hoist or other
lifting device.
Carefully lift the unit and secure it to the wall.
Refer to 8 Appendix for dimensional drawings to
determine fasteners size and location.
3.2.3 Forklift
Only a competent lift operator with additional
support personnel should attempt moving the
unit.
Carefully position forklift and ensure stability prior
to lift.
3.2.4 Shipping Weights
Weights listed in Table 3.7 are approximate for base units.
Options can add or reduce weight of unit. Weights listed
are in lbs.
Frame Non Bypass Panel Bypass Panel
P2 36 84
P3 66 106
P4 106 167
P5 155 248
Table 3.7 Approximate Shipping Weights
Installation
BAS-SVX49A-EN 3-3