Trane PRC001-EN Air Conditioner User Manual


 
51RT-PRC001-EN
*Indicates both downflow and horizontal units.
Electrical
Data (High Efficiency)
Table ED-9 — Unit Wiring - Dehumidification (Hot Gas Reheat) Option (Downflow Only)
Standard Indoor Fan Motor Oversize Indoor Fan Motor
Unit Minimum Maximum Fuse Minimum Maximum Fuse
Unit Operating Circuit Size or Maximum Circuit Size or Maximum
Tons Model No. Voltage Range Ampacity
2
Circuit Breaker
1
Ampacity
2
Circuit Breaker
1
YCD151C3 187-253 59 70 65 80
12½ YCD151C4 414-506 30 35 32 40
YCD151CW 517-633 24 30 26 30
YCD181C3 187-253 71 90 77 100
15 YCD181C4 414-506 36 45 39 50
YCD181CW 517-633 28 35 30 40
YCD241C3 187-253 98 125 105 125
20 YCD241C4 414-506 50 60 53 60
YCD241CW 517-633 39 50 42 50
Notes:
1. HACR breaker per NEC.
2. MCA values do not include Power Exhaust accessory. See Table ED-7 for this information.