Trane PRC001-EN Air Conditioner User Manual


 
RT-PRC001-EN38
(15 Ton)
High Efficiency
Performance
Data
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
For Standard Motor and High Static Drive (RPM), reference Table PD-32.
For Oversize Evaporator Fan Speed (RPM), reference Table PD-33.
Data includes pressure drop due to filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-36 to determine add’l static pressure drop due to other options/accessories
Fan motor heat (MBH) = 3.15 x Fan Bhp.
Notes:
1. Field Supplied Fan Sheave BK120 required. Field Supplied Belt May be necessary.
Table PD-25— Evaporator Fan Performance — 15 Ton — YC*181C— Standard or TXV Refrigeration System
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Field Supplied Low Static Drive (1) 3 HP Standard Motor & Drive
4800 414 0.81 450 0.94 483 1.06 515 1.20 548 1.35 578 1.50 609 1.66 640 1.83 668 2.00 694 2.18
5400 456 1.11 490 1.26 520 1.39 549 1.54 578 1.70 607 1.87 635 2.03 662 2.21 689 2.39 716 2.58
6000 499 1.48 531 1.65 559 1.81 585 1.96 611 2.12 638 2.29 664 2.48 689 2.67 714 2.85 738 3.05
6600 542 1.92 572 2.12 599 2.3 624 2.46 648 2.63 671 2.81 695 3.00 719 3.20 743 3.41 765 3.62
7200 586 2.45 614 2.67 640 2.88 663 3.06 686 3.24 708 3.42 729 3.61 751 3.82 773 4.04 795 4.26
5 HP Oversized Motor & Drive
Factory supplied motors, in commercial equipment, are definite
purpose motors, specifically designed and tested to operate reliably
and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
Table PD-25 — Evaporator Fan Performance — 15 Ton— YC*181C — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Drive 3 HP Standard Motor & High Static Drive Accessory
\4800 719 2.36 744 2.55 769 2.75 792 2.95 815 3.14 838 3.34 859 3.54 880 3.73 901 3.93 921 4.13
5400 742 2.77 766 2.97 789 3.17 811 3.38 833 3.59 855 3.81 876 4.03 897 4.26 917 4.48 937 4.70
6000 763 3.25 788 3.46 811 3.68 833 3.89 855 4.11 875 4.33 896 4.56 916 4.80 935 5.04 955 5.28
6600 788 3.82 810 4.03 832 4.26 855 4.49 877 4.72 898 4.96 918 5.20 937 5.43 956 5.67
7200 816 4.49 837 4.71 857 4.94 989 5.17 898 5.41 919 5.66 ———————
5 HP Oversized Motor & Drive
*Indicates both downflow and horizontal units.
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
For Standard Motor and High Static Drive (RPM), reference Table PD-32.
For Oversize Evaporator Fan Speed (RPM), reference Table PD-33.
Data includes pressure drop due to filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-36 to determine add’l static pressure drop due to other options/accessories
Fan motor heat (MBH) = 3.15 x Fan Bhp.
Notes:
1. Field Supplied Fan Sheave BK120 required. Field Supplied Belt may be necessary.
Factory supplied motors, in commercial equipment, are definite
purpose motors, specifically designed and tested to operate reliably
and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
Table PD-26— Evaporator Fan Performance — 15 Ton — Y*D181C — Dehumidification (Hot Gas Reheat) Option
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Field Supplied Low Static Drive (1) 3 HP Standard Motor & Drive
4800 427 0.88 463 1.03 496 1.16 527 1.31 557 1.46 586 1.61 614 1.77 641 1.93 667 2.10 693 2.29
5400 471 1.21 505 1.38 535 1.53 564 1.69 591 1.85 618 2.02 644 2.19 669 2.36 695 2.54 718 2.72
6000 516 1.61 547 1.81 576 1.98 603 2.15 628 2.33 653 2.51 677 2.70 700 2.88 724 3.07 747 3.26
6600 561 2.09 590 2.32 617 2.52 643 2.71 667 2.90 690 3.09 712 3.29 734 3.49 756 3.70 777 3.90
7200 607 2.67 634 2.92 659 3.16 683 3.36 707 3.56 728 3.77 749 3.98 770 4.20 791 4.42 811 4.64
5 HP Oversized Motor & Drive
Table PD-26 — Evaporator Fan Performance — 15 Ton— Y*D181C — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Drive 3HP Motor and High Static Drive Accessory 5 HP Oversized Motor & Drive
4800 719 2.49 742 2.69 765 2.89 787 3.09 808 3.28 829 3.48 849 3.68 869 3.89 887 4.09 906 4.29
5400 742 2.91 765 3.12 788 3.34 810 3.56 831 3.79 852 4.01 872 4.24 891 4.46 909 4.67 928 4.91
6000 769 3.46 791 3.66 812 3.87 833 4.09 855 4.33 874 4.57 894 4.81 913 5.06 932 5.31 950 5.56
6600 799 4.11 819 4.32 840 4.53 860 4.75 879 4.98 899 5.22 918 5.46 937 5.72
7200 830 4.86 850 5.09 870 5.31 888 5.54 ———————