Trane PRC001-EN Air Conditioner User Manual


 
RT-PRC001-EN16
General Data
(25 Ton)
Standard Efficiency
Table GD-3 — General Data
25 Ton Downflow and Horizontal Units
YC*300B3,B4,BWL, BK YC*300B3,B4,BWH, BK
Cooling Performance
1
Gross Cooling Capacity 290,000
EER
2
9.7
Nominal CFM / ARI Rated CFM 10,000 / 8,750
ARI Net Cooling Capacity 272,000
Integrated Part Load Value
3
9.8
System Power (KW) 28.05
Heating Performance
4
Heating Models Low High
Heating Input (Btuh) 250,000 400,000
1st Stage 175,000 300,000
Heating Output (Btuh) 203,000 324,000
1st Stage 142,000 243,000
AFUE (%)
5
Downflow/Horizontal 80.2/81.0 79.8/79.7
Steady State Efficiency (%) 81.4/81.0 80.8/81.0
No. Burners 1
No. Stages 2
Gas Supply Pressure (in. w.c)
Natural or LP (minimum/maximum) 2.5/14.0
Gas Connection Pipe Size (in.) 1/2 3/4
Compressor
No./Type 2/Scrolls
Sound Rating (BELS)
6
9.4
Outdoor Coil - Type Hi-Performance
Tube Size (in.) OD .375
Face Area (sq ft) 36.43
Rows/FPI 2/16
Indoor Coil - Type Hi-Performance
Tube Size (in.) .375
Face Area (sq ft) 26.00
Rows/FPI 3/15
Refrigerant Control Short Orifice
Drain Connection No./Size (in.) 1/1.00 NPT
Outdoor Fan - Type Propeller
No. Used/Diameter (in.) 2/28
Drive Type/No. Speeds Direct/1
CFM 16,700
No. Motors/HP 2/1.0
Motor RPM 1,125
Indoor Fan - Type FC Centrifugal
No. Used/Diameter (in.) 1/18 X 18
Drive Type/No. Speeds Belt/1
No. Motors 1
Motor HP (Standard/Oversized)
9
7.5/NA
Motor RPM (Standard/Oversized)
9
3470/NA
Motor Frame Size (Standard/Oversized)
9
184T/NA
Filters - Type Furnished
8
Throwaway
(No.) Size Recommended
Downflow (4) 20 X 20 X 2(4) 20 X 25 X 2
Horizontal (8) 20 X 25 X 2
Refrigerant Charge (Lbs of R-22)
7
Downflow
Horizontal 17.0/Circuit
Notes:
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes
the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. YC*300B model ratings shown are tested in accordance with ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI rated cfm.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown
are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
5. AFUE is rated in accordance with DOE test procedures.
6. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
7. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
8. An optional 2 inch pleated filter is also available.
9. For 380V/60Hz units, the oversized mtoor is used as the standard motor. Refer to oversized motor data.
*Indicates both downflow and horizontal units.