RT-PRC001-EN22
Performance
Data
(15, 17½ Ton)
Standard Efficiency
Table PD-2 — Gross Cooling Capacities (MBH) 15 Ton Three Phase YC*180B3, B4, BW, BK
Ambient Temperature
85 95 105 115
Enter.
Dry Entering Wet Bulb
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 168.0133.0188.0106.0198.0 73.0 157.0128.0181.0101.0194.0 70.4 147.0122.0172.0 97.0 187.0 67.3 137.0 117.0 162.0 92.1 179.0 63.2
80 168.0156.0 188.0 128.0 199.0 97.3 155.0 155.0 181.0 125.0 195.0 94.3 149.0 143.0 172.0 120.0 188.0 90.8 140.0 137.0 162.0 115.0 179.0 86.7
5400
85 174.0174.0 189.0 150.0 200.0 117.0 166.0 166.0 182.0 147.0 196.0 115.0 158.0 158.0 172.0 143.0 189.0 113.0 150.0150.0 162.0 138.0 180.0 110.0
90 184.0184.0 190.0 172.0202.0 136.0 177.0 177.0 183.0 170.0 197.0 135.0 170.0 170.0170.0 170.0 190.0 133.0 162.0 162.0 165.0 157.0 181.0 131.0
75 172.0140.0190.0 110.0 199.0 74.3 161.0134.0184.0106.0195.0 71.7 151.0129.0175.0101.0189.0 68.7 140.0124.0165.0 96.1 181.0 64.9
80 169.0169.0 191.0 133.0 200.0 99.4 164.0 157.0 184.0 130.0 196.0 97.2 155.0 151.0 176.0 126.0 190.0 93.8 145.0 145.0 165.0 121.0 182.0 89.9
6000
85 181.0 181.0 192.0 156.0 202.0 119.0 173.0 173.0 185.0 154.0 198.0 118.0 165.0 165.0 176.0 151.0 191.0 116.0 157.0 157.0 166.0 146.0183.0 113.0
90 189.0189.0 193.0 179.0204.0 140.0 183.0 183.0 183.0183.0 199.0 139.0 176.0 176.0 178.0 171.0 193.0 138.0168.0 168.0 170.0 166.0 184.0136.0
75 176.0 147.0 192.0 112.0200.0 75.5 165.0141.0186.0110.0 196.0 73.0 154.0136.0178.0105.0190.0 69.8 144.0130.0168.0 99.8 182.0 66.1
80 178.0 171.0 193.0 136.0 201.0 101.0 169.0 165.0 187.0 135.0 197.0 98.8 160.0 159.0178.0 131.0 191.0 96.1 150.0 150.0 168.0 127.0 183.0 92.6
6600
85 185.0185.0 194.0 161.0 203.0 122.0 179.0 179.0 188.0160.0 199.0 121.0 171.0 171.0 179.0 158.0 193.0 119.0 163.0 163.0 169.0 153.0 185.0 116.0
90 193.0 193.0 193.0 193.0 205.0 143.0 188.0 188.0188.0 188.0 201.0 143.0 181.0 181.0 182.0 178.0 195.0 142.0173.0 173.0 174.0 174.0 186.0140.0
75 179.0152.0194.0 114.0 201.0 76.7 168.0147.0188.0112.0 197.0 74.2 158.0142.0180.0109.0191.0 71.0 142.0142.0170.0103.0183.0 67.2
80 182.0 177.0 195.0 140.0 202.0 103.0 173.0172.0 189.0 139.0 198.0 100.0 164.0 164.0 181.0 136.0 192.0 97.6 155.0 155.0 171.0 132.0184.0 94.4
7200
85 189.0189.0 196.0 166.0204.0 125.0 183.0 183.0 190.0 166.0 200.0 123.0 176.0 176.0 182.0164.0 194.0 121.0 167.0 167.0 167.0 167.0 186.0 119.0
90 197.0 197.0 197.0 197.0 206.0146.0 192.0 192.0 193.0 187.0 202.0 146.0 185.0 185.0 186.0184.0 196.0 146.0 177.0 177.0 177.0 177.0 188.0 144.0
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
*Indicates both downflow and horizontal units.
Table PD-3 — Gross Cooling Capacities (MBH) 17½ Ton Three Phase YC*210C3, C4, CW, CK
Ambient Temperature
85 95 105 115
Enter
Dry Entering Wet Bulb
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 195.0 171.0 213.0 127.0 224.0 83.3 182.0 164.0 206.0 124.0 219.0 80.1 169.0 158.0 195.0 119.0 213.0 76.1 155.0 151.0 181.0 113.0 204.0 71.8
80 200.0200.0 214.0 157.0 226.0 114.0 191.0 191.0 207.0 156.0 221.0 112.0 180.0 180.0 196.0 153.0 214.0 110.0 168.0168.0 183.0 147.0 205.0 106.0
6300
85 211.0 211.0 217.0 188.0 229.0 140.0 204.0 204.0 209.0188.0 223.0 139.0 195.0 195.0 199.0 186.0 216.0 139.0 184.0 184.0 187.0 182.0 206.0 137.0
90 219.0 219.0 220.0 217.0 230.0 164.0214.0 214.0 214.0 214.0 225.0 167.0 207.0 207.0 207.0 207.0 218.0 169.0 198.0 198.0 198.0 198.0 208.0 168.0
75 199.0 181.0 215.0 131.0 225.0 84.7 187.0 176.0 208.0 129.0 221.0 81.4 174.0 169.0 198.0 125.0 215.0 77.7 160.0 160.0 185.0 119.0 206.0 73.4
80 206.0206.0 217.0 164.0 228.0 116.0 198.0 198.0 210.0 164.0 222.0 114.0 188.0188.0 200.0 162.0 216.0 113.0 176.0 176.0 187.0 157.0 207.0 110.0
7000
85 216.0216.0 220.0 197.0 230.0144.0 210.0 210.0 213.0 198.0 225.0 144.0 202.0 202.0 204.0 198.0 218.0 145.0 192.0 192.0 192.0 192.0 209.0 144.0
90 224.0224.0 224.0 224.0 233.0 172.0 219.0 219.0 219.0 219.0 227.0 173.0 212.0 212.0 212.0 212.0 221.0 177.0 204.0 204.0 204.0 204.0 211.0 177.0
75 203.0 191.0 217.0 135.0 226.0 86.1 192.0 187.0 211.0 138.0 222.0 82.9 178.0 178.0 201.0 131.0 216.0 79.2 165.0 165.0 188.0126.0 208.0 75.0
80 211.0 211.0 219.0 169.0 229.0 118.0 204.0 204.0 212.0 171.0 224.0 117.0 194.0 194.0 203.0 170.0 218.0 116.0 183.0 183.0 191.0 167.0 209.0 114.0
7700
85 220.0220.0 222.0 203.0 232.0 147.0 214.0 214.0 216.0 207.0 226.0 148.0 207.0 207.0 207.0 207.0 220.0 150.0 197.0 197.0 197.0 197.0 211.0 150.0
90 226.0226.0 226.0 226.0 235.0 176.0 223.0 223.0222.0 222.0 229.0 179.0 216.0216.0 216.0 216.0 223.0 184.0 208.0208.0 208.0 208.0 214.0 186.0
75 206.0 199.0 218.0 138.0 227.0 87.8 195.0 195.0 212.0 143.0 223.0 84.3 183.0 183.0 203.0 136.0 217.0 80.6 171.0 171.0 190.0 132.0 209.0 76.5
80 214.0214.0 221.0 174.0 230.0 120.0 208.0 208.0214.0 178.0 226.0 120.0 199.0 199.0 205.0 178.0 219.0 119.0 188.0 188.0 194.0 176.0 211.0 117.0
8400
85 222.0222.0 224.0 210.0 233.0 150.0 217.0 217.0 218.0 215.0 228.0 151.0 211.0 211.0 211.0 211.0 222.0 155.0 202.0 202.0 202.0 202.0 213.0 156.0
90 229.0229.0 229.0 229.0 236.0 181.0 225.0 225.0 225.0 225.0 231.0 184.0 220.0220.0 219.0 219.0 225.0 190.0 212.0212.0 212.0 212.0 216.0 193.0
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
table notes.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity