Trane PRC001-EN Air Conditioner User Manual


 
25RT-PRC001-EN
Performance
Data
(15 Ton)
High Efficiency
Table PD-8— Gross Cooling Capacities (MBH) 15 Ton Three Phase YC*181C3, C4, CW— Standard Refrigeration System
Ambient Temperature
85 95 105 115
Enter.
Dry Entering Wet Bulb
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 172 144 194 112 205 75.2 159 138 185 107 200 71.9 147 131 172 101 193 68 130 130 158 97 183 63.4
80 175 169 195 138 207 103 164 162 186 134 202 99.7 153 153 173 128 194 95.4 142 142 158 122 183 90.5
5400
85 185 185 196 164 209 126 176 176 186 161 203 124 165 165 174 156 195 122 155 155 155 155 184 117
90 195 195 195 195 211 149 188 188 190 184 204 148 178 178 179 179 196 147 168 168 167 167 184 144
75 177 153 197 116 207 76 164 147 189 112 202 73.2 151 140 176 106 195 69.3 138 131 162 99.8 185 64.8
80 181 180 198 144 209 105 170 170 189 142 204 103 159 159 177 136 196 99.4 148 148 162 130 186 94.6
6000
85 192 192 199 172 211 129 183 183 190 171 206 129 173 173 173 173 197 127 162 162 162 162 186 124
90 201 201 200 200 214 153 194 194 195 194 208 155 185 185 185 185 199 154 175 175 175 175 187 152
75 181 162 198 123 208 76.6 168 155 191 117 204 74.4 152 152 180 111 197 70.6 142 139 165 105 187 66.2
80 186 186 200 151 210 107 177 177 192 148 206 105 166 166 180 144 198 102 154 154 166 137 188 98.6
6600
85 197 197 202 179 213 131 189 189 194 180 208 132 179 179 183 173 199 132 168 168 170 166 189 129
90 204 204 205 202 215 157 199 199 199 199 209 159 191 191 191 191 201 160 181 181 181 181 190 160
75 184 170 200 127 209 79.1 168 168 193 121 206 76.4 156 156 182 116 198 71.9 145 145 168 110 189 67.4
80 191 191 202 153 211 108 182 182 194 154 207 107 171 171 183 151 199 105 159 159 169 145 190 102
7200
85 200 200 204 185 214 134 194 194 194 194 209 136 185 185 187 181 201 135 174 174 174 174 191 134
90 207 207 208 207 217 160 203 203 203 203 211 163 195 195 195 195 203 166 186 186 186 186 192 167
Notes:
1 All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-9— Gross Cooling Capacities (MBH) 15 Ton Three Phase Y*D181C3, C4, CW— Dehumidification (Hot Gas Reheat) or TXV Option
Ambient Temperature
85 95 105 115
Enter.
Dry Entering Wet Bulb
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 170.7 136.0 190.4 106.1 211.6 75.2 162.3 131.1 181.4 101.4 201.8 70.6 153.6 126.0 172.0 96.5 191.5 65.9 144.5 120.8162.0 91.4 180.7 61.0
80 171.7 160.6 190.8 130.7 211.9 100.2 160.6 160.6 181.9 125.9 202.1 95.5 153.2 153.2 172.4 121.0 191.9 90.7 146.9 139.9 162.3 115.8 181.1 85.8
4800
85 177.7 174.7 191.1 154.8 212.4 124.6 170.2168.8 182.2 150.0 202.6 119.9 162.7 162.7 172.9144.9 192.4 115.0 154.8 154.8 163.1 139.7 181.6 110.0
90 187.3 187.3 192.5 179.3212.8 148.8 180.0 180.0 179.9179.9 203.0 144.1 172.3 172.3 174.8164.7 192.6 139.0 164.2 164.2 166.1 157.7 181.9 133.9
75 174.9 144.5 194.5 112.1 216.0 77.0 166.3 139.5 185.3 107.3 205.8 72.4 157.3 134.3 175.6 101.5 195.2 67.6 147.9 129.0 165.4 96.4 184.0 62.7
80 174.5 174.5 194.9 138.5 216.4 104.7 168.9 161.1 185.6 133.5 206.3 99.9 160.7 156.2175.9 128.4 195.7 95.0 152.2 147.5 165.8 123.2 184.6 90.0
5400
85 184.9 184.9 195.7 165.2 216.9 131.7 177.3 177.3 186.6 160.3 206.8 126.9 169.4169.4 177.0 155.3 196.2 122.0 161.1 161.1 166.9 150.0 185.2 116.9
90 195.2 195.2 195.2 195.2 217.1 158.5 187.5 187.5 189.8 182.7 207.1 153.6 179.4 179.4 181.1 173.6 196.5 148.5170.9 170.9 172.1 166.5 185.6143.3
75 178.4 152.6 198.2 116.1 219.6 78.7 169.6 147.6 188.6 111.3 209.2 74.0 160.5 142.3178.6 106.3 198.2 69.2 150.9 137.0 168.1 101.1 186.8 64.3
80 182.0 177.3 198.5 145.8 220.1 108.9 174.1 168.5189.0 140.8 209.7 104.1 165.7 161.8 179.0135.7 198.8 99.2 156.8 154.9 168.6130.4 187.5 94.1
6000
85 191.4 191.4 199.7 175.4 220.7 138.6 183.6 183.6 190.3 170.4 210.3 133.8 175.4 175.4 180.5165.2 199.4 128.8 166.7 166.7 166.6 166.6 187.8 123.6
90 202.3 202.3 204.1 198.8 221.0 167.8 194.3 194.3 195.6 189.2 210.7 162.8 185.8185.8 186.7 182.3 200.0 157.7 176.9 176.9 177.3 175.3 188.8 152.5
75 181.5 160.5 201.1 120.8222.6 80.3 172.6 155.4 191.4 115.9 212.0 75.6 163.3 150.2 181.1 110.9 200.8 70.8 150.6 150.6 170.4105.7 189.1 65.7
80 186.8 182.2 201.6 153.0 223.2 113.0 178.6 175.7 191.9 147.9 212.6 108.2 170.0 169.1 181.8 142.7 201.5 103.2 161.0 161.0 171.1 137.4 189.9 98.1
6600
85 197.1 197.1 203.2 185.2223.8 145.3 189.1 189.1 193.7 180.2 212.9 140.3 180.5 180.5 180.4180.4 201.9 135.2 171.5 171.5 171.4 171.4 190.3 129.9
90 208.4 208.4 209.5 204.4 224.3176.8 200.1 200.1 200.8 197.7 214.0 171.8 191.4 191.4 191.5 190.9 203.0 166.7 182.1 182.1182.1 182.1 191.5 161.4
75 184.4 168.2 203.7 125.4 225.2 81.9 175.3 163.1 193.7 120.5 214.3 77.0 163.0 163.0 183.0 115.3 202.9 72.1 154.3 154.3 172.2 109.9 191.0 67.1
80 191.1 189.2 204.2159.9 225.9 116.9 182.5182.5 194.4 154.9 215.0 112.0 174.0 174.0 184.1 149.7 203.7 107.1 165.0 165.0 173.3 144.2 191.9 101.9
7200
85 202.2 202.2 202.1 202.1 226.2 151.6 193.9 193.9 193.8 193.8 215.5 146.5 185.1 185.1 187.2 181.0 204.2 141.4 175.8 175.8 177.4 169.9 192.5 136.0
90 214.0 214.0 214.4 212.7 227.3 185.7 205.3 205.3205.2 205.2 216.8 180.7 196.3 196.3 196.2 196.2 205.6 175.5 186.8 186.8 186.7 186.7 194.0 170.1
Notes:
1 All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow
table notes.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
*Indicates both downflow and horizontal units.