Toshiba RAV-SM806KRT-TR Air Conditioner User Manual


 
No.
6
Item
Fan speed control
(Continued)
Outline of specifications
Remarks
“PRE-HEAT
indication
7 Cool air discharge
preventive control
1) In heating operation, the indoor fan is controlled based on
the detected temperature of Tc sensor or Tcj sensor. As
shown below, the upper limit of the revolution frequency is
restricted.
However B zone is assumed as C zone for
6 minutes and after when the compressor activated.
In defrost operation, the control value of Tc or Tcj is shifted
by
6°C.
In D and E zones, the
priority is given to air
volume selection
setup of remote
controller.
Tc, Tcj
˚C
32
30
28
26
20
16
HH
H
L
UL
OFF
E zone
D zone
C zone
B zone
A zone
FILE NO. SVM-12004
31
Ta
˚C
HH
HH+α
47
42
3) When thermo sensor turns OFF during heating, the fan
speed mode becomes UL ( weak).
4) When Ta is 25°C or above at the beginning of HEAT
operation or when canceling defrost mode, H or HH mode
continues for 1 minute from the time when Tc enters zone
E. (Following figure.)
5) The HH fan speed for auto cooling/heating is set to a
speed higher than that for normal cooling/heating.
However, it varies depending on the temperature difference
of Tc during auto heating.
COOL
HH
H+
H
L+
L
UL
HEAT
HH
H+
H
L+
L
UL
SM56
1080
1080
1020
1000
980
980
940
900
500
SM80
1260
1240
1080
1020
980
980
940
900
500
Fan speed [rpm]