Toshiba RAV-SM806KRT-TR Air Conditioner User Manual


 
A
ØD
d) Flare Processing
Make certain that a clamp bar and copper
pipe have been cleaned.
By means of the clamp bar, perform the flare
processing correctly.
Use either a flare tool for R410A or conven-
tional flare tool.
Flare processing dimensions differ according
to the type of flare tool.
When using a conventional flare tool, be sure
to secure “dimension A” by using a gauge for
size adjustment.
Fig. 6-2-1 Flare processing dimensions
Table 6-2-3 Dimensions related to flare processing for R410A
Table 6-2-4 Dimensions related to flare processing for R22
Table 6-2-5 Flare and flare nut dimensions for R410A
Nominal
diameter
1/4
3/8
1/2
5/8
Outer
diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
A (mm)
Flare tool for R410A
Conventional flare tool
clutch type
Clutch type Wing nut type
0 to 0.5 1.0 to 1.5 1.5 to 2.0
0 to 0.5 1.0 to 1.5 1.5 to 2.0
0 to 0.5 1.0 to 1.5 2.0 to 2.5
0 to 0.5 1.0 to 1.5 2.0 to 2.5
Nominal
diameter
1/4
3/8
1/2
5/8
Outer
diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
A (mm)
Flare tool for R22
Conventional flare tool
clutch type
Clutch type Wing nut type
0 to 0.5 0.5 to 1.0 1.0 to 1.5
0 to 0.5 0.5 to 1.0 1.0 to 1.5
0 to 0.5 0.5 to 1.0 1.5 to 2.0
0 to 0.5 0.5 to 1.0 1.5 to 2.0
Nominal
diameter
1/4
3/8
1/2
5/8
Outer diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
Dimension (mm)
ABCD
9.1 9.2 6.5 13
13.2 13.5 9.7 20
16.6 16.0 12.9 23
19.7 19.0 16.0 25
Flare nut width
(mm)
17
22
26
29
FILE NO. SVM-12004
20