– 81 –
NO
Correct connection of connector.
Check CDB.
Defect
Replace
* Refer to Characteristics-3.
YES
NO
Are characteristics of TE/TS sensor
resistance values normal?
Replace TE and TS sensors.
YES
NO
Is connection of TD sensor connector
of CDB CN600 normal?
Correct connection of connector.
Check control P.C. board.
Defect
Replace
* Refer to Characteristics-4.
YES
NO
Are characteristics of TD sensor
resistance value normal?
Replace TD sensor.
YES
NO
Is connection of TO sensor connector
of CDB CN601 normal?
Correct connection of connector.
Check CDB.
Defect
Replace
* Refer to Characteristics-5.
* (For RAV-SM560AT-E, CN602 TO sensor)
YES
NO
Are characteristics of TO sensor
resistance value normal?
Replace TO sensor.
YES
* (For RAV-SM560AT-E, CN600 TE sensor and CN603 TS sensor)
* (For RAV-SM560AT-E, CN601 TD sensor)
Are connections of
TE/TS sensor connectors of
CDB CN604/CN605 normal?
[F06 error]/[18 error]
[F04 error]/[19 error]
[F08 error]/[1b error]