Toshiba RAV-SM800AT-E Air Conditioner User Manual


 
– 43 –
No.
9
Item
Drain pump control
(For the duct, when
the drain-up kit
(sold separately) is
mounted)
Outline of specifications
1) In cooling operation (including Dry operation), the
drain pump is usually operated.
2) If the float switch operates while drain pump
operates, the compressor stops, the drain pump
continues the operation, and a check code is
output.
3) If the float switch operates while drain pump stops,
the compressor stops and the drain pump oper-
ates. If the float switch keeps operating for approx.
4 minutes, a check code is output.
Remarks
Check code [P10]
When heating operation stops, the indoor fan operates
with LOW mode for approx. 30 seconds.
10
11
After-heat elimina-
tion
All modes
In group twin/triple operation, the swinging
positions can be set up collectively or individu-
ally.
3) When the unit stops or when a warning is output,
the flap automatically moves downward.
4) While the heating operation is ready, the flap
automatically moves upward.
1) Flap position setup
When the flap position is changed, the position
moves necessarily to downward discharge
position once to return to the set position.
The flap position can be set up in the following
operation range.
Flap control
(For 4-way air
discharge cassette
type only)
Warning :
A check code is displayed
on the remote controller,
and the indoor unit stops.
(Excluding [F08] and
[L31])
In cooling/dry operation In heating/fan operation
In group twin/triple operation, the flap positions
can be set up collectively or individually.
2) Swing setup
The swinging position can be moved in the
following operation range.