Toshiba RAV-SM800AT-E Air Conditioner User Manual


 
74
Correct cable connection
Correct central control network address.
Check operation cause.
Check indoor P.C. board
(MCC-1402 or MCC-1403).
Defect
Replace
Check indoor P.C. board
(MCC-1402 or MCC-1403).
Defect
Replace
Check indoor P.C. board
(MCC-1402 or MCC-1403).
Defect
Replace
Check outside devices.
Defect
Replace
Check corresponding
indoor/outdoor units.
Check central controller
(including network adapter).
Defect
Replace.
NO
NO
YES
NO
NO
NO
NO
YES
YES
YES
NO
YES
YES
YES
YES
Are cable connections to
communication line X, Y normal?
Is indoor remote controller
[L20] displayed?
Is central controller [98] displayed?
Are outside devices of
connector CN80 connected?
Is check code displayed on sub unit
of main or sub remote controller?
Do outside devices normally operate?
Is group operation performed?
Are not multiple
same central control network
addresses connected?
[L20 error]/[98 error]
[L30 error]/[B6 error]
[b7 error] (Central controller)