Toshiba RAV-SM800AT-E Air Conditioner User Manual


 
160
RAV-SM800AT-E
No.
Part name
Common
procedure
Procedure
CAUTION
Never forget to put on the gloves at
working time, otherwise an injury will be
caused by the parts, etc.
1. Detachment
1) Stop operation of the air conditioner, and
also turn off switch of the breaker.
2) Remove the front panel.
(ST1T Ø4 x 10L, 3 pcs.)
After taking off screws, remove the front
panel by pulling it downward.
3) Disconnect the connecting cables and
power cord from the terminals and cord
clamp.
4) Remove the upper cabinet.
(ST1T Ø4 x 10L, 6 pcs.)
2. Attachment
1) Attach the waterproof cover.
CAUTION
Be sure to attach a waterproof cover.
If it is not attached, there is a possibility
that water enters inside of the outdoor unit.
2) Attach the upper cabinet.
(ST1T Ø4 x 10L, 6 pcs.)
3) Connect the connecting cable and power
cord at the terminal and fix them with cord
clamp.
CAUTION
Using bundling band sold at a market, be
sure to fix the power cables and indoor/
outdoor connecting cables along the inter-
unit cable so that they do not come to
contact with the compressor, valves and
cables at gas side, and the discharge pipe.
4) Attach the front cabinet.
(ST1T Ø4 x 10L, 3 pcs.)
Remarks
Front
cabinet
Upper plate
of cabinet
Water-proof
cove