– 115 –
14-2-2. Remote controller with timer
RBC-AM1E
1. Operation for CHECK display
When pushing the CHECK switch, the indoor unit No. (Group address No.) which sends the check code is
displayed in the set up temp. display section, and check code is displayed in the TIME display section.
If FILTER display (air filter cleaning sign) is present, the indoor unit No. which sends the filter signal is dis-
played in the set up temp. display section, and then the check code is displayed. (1 display for 3 seconds)
ON/OFF
MODE
TIMER ADJUST
CHECK FILTER
REMOTE CONTROLLER
MODE
FAN ONLY
COOL
HEAT
TEMP
UNIT
CHECK
DEMAND
TIMER
LOUVER
MANUAL
FAN
AUTO
HIGH
MED
LOW
FIX
PREHEAT
DEFROST
OPERATION
STANDBY
FILTER
C
F
CONT.OFF ON ADDRESS
AFTER
H
M
(This display is for remote control with timer.)
LCD display STANDBY is present.
• When phase-sequence of power wiring is incorrect
• When combination of indoor units is over capacity.
• Indoor unit with command excepted by operation mode select switch
• When there is an indoor unit which stopped with the indoor overflow alarm “0b”.
• Indoor unit with cooling operation command excepted by heating priority control
CHECK switch
Push for 0.5 seconds to display CHECK code.
Push for 3 seconds to reset indoor microprocessor.
(While indoor microprocessor is locked by ALL STOP alarm)
Push for 10 seconds to clear check data.
RESET switch
Push the switch in
the hole with pin.
The remote controller
resets initialized.
(All data is cleared.)