34
F5 F4
47
42
F5
Tc
(˚C)
–1.0
Ta (˚C)
E
D
C
B
A
(-0.5)
L(L)
L(H)
H(H)
H
HH
(HH)
(HH)
+1.0
(+0.5)
+2.0
(+1.0)
+3.0
(+1.5)
+4.0
(+2.0)
Tsh
(0)
No.
5
Item
Air speed
selection
(Continued)
Outline of specifications
<HEAT>
Value in the parentheses indicates one when thermostat of
the remote controller works.
Value without parentheses indicates one when thermostat
of the body works.
• If the air speed has been changed once, it is not
changed for 1 minute. However when the air speed is
exchanged, the air speed changes.
• When heating operation has started, the air speed
selects a upward slope, that is, the high position.
• If the temperature is just on the difference boundary, the
air speed does not change.
• Mode in the parentheses indicates one in automatic
heating operation.
• In Tc ≥ 60°C, the air speed increases by 1 step.
3) In heating operation, the mode changes to [UL] if
thermostat is turned off.
4) If Ta ≥ 25°C when heating operation has started and
when defrost operation has been cleared, it operates
with HIGH (H) mode or (HH) for 1 minute from when Tc
has entered in E zone of cool air discharge preventive
control (Item 6).
5) In automatic cooling/heating operation, the revolution
frequency of [HH] is set larger than that in the standard
cooling/heating operation. However the revolution
frequency is restricted in the automatic heating opera-
tion as shown in the following figure.
Remarks
[PRE-HEAT] display
(˚C)
32
30
28
26
20
16
Tc
Tcj
HH
H
L
UL
OFF
E zone
D zone
C zone
B zone
A zone
6 Cool air
discharge
preventive
control
In D or E zone, the priority
is given to setup of air
volume exchange.
In A and B zones,
[PRE-HEAT] is displayed.
1) In heating operation, the indoor fan is controlled based
on the detected temperature of Tc sensor or Tcj sensor.
As shown below, the upper limit of the revolution
frequency is determined.