4 SELECTION OF INSTALLATION PLACE
Upon customer’s approval, install the air conditioner in a place which satisfies the following conditions:
Place where it can be installed horizontally.
Place which can reserve a sufficient service space for safe maintenance or checks.
Place where there is no problem even if the drained water overflows.
Avoid the following places:
Salty places (seaside area) or places with much gas sulfide (hot spring area) (If selecting such a place, special
maintenance is required.)
Places where oil (including machine oil), steam, oil smoke or corrosive gas is generated.
Places where an organic solvent is used.
Chemical plants with a cooling system using liquid carbon dioxide.
Places where a device generating high frequency (inverter, non-utility generator, medical apparatus, or
communication equipment) is set. (Malfunction or abnormal control of the air conditioner, or interference to
devices listed above may occur.)
Places where discharged air from the outdoor unit blows against the windows of a neighbour's house.
Places unable to bear the weight of the unit.
Places with poor ventilation.
Installation space
Leave space necessary for running, installation and servicing.
NOTE
If there is an obstacle above the outdoor unit, leave a space of 2000mm or more to the top end of the outdoor unit.
If there is a wall around the outdoor unit, make sure that its height does not exceed 800mm.
Air discharge
Air intake
Air intake
Air intake
Air intake
Installation/servicing
surface
Square hole for
handling
Outdoor unit top view
10mm or more
500mm or more
(Rear side)
10mm or more
500mm or more
(Front side)
20mm or more
20mm or more