Toshiba MMY-MAP1004HT8-E Air Conditioner User Manual


 
–11–
SMMS-i
Installation Manual
SMMS-i
Installation Manual
Coupling size of brazed pipe
(Unit: mm)
Selection of pipe size
Capacity code of indoor and outdoor units
Selection of pipe material
For the indoor unit, the capacity code is decided at each capacity rank. (Table 1)
The capacity codes of the outdoor units are decided at each capacity rank. The maximum number of connectable
indoor units and the total value of capacity codes of the indoor units are also decided. (Table 2)
NOTE
Compared with the capacity code of the outdoor unit, the total value of capacity codes of the connectable indoor units differs
based on the height difference between the indoor units.
When the height difference between the indoor units is 15m or less: Up to 135% of the capacity code (Equivalent
to HP) of the outdoor unit (Equivalent to HP) of the outdoor unit
When the height difference between the indoor units is over 15m: Up to 105% of the capacity code
Connected section
External size Internal size
Standard outer dia.
of connected
copper pipe
Connected section
Min. thickness
of coupling
External size Internal size
Min. depth of
insertion
Oval value
Standard outer dia.
(Allowable difference)
CFKG
6.35 6.35 (±0.03) 6.45 ( ) 7 6 0.06 or less 0.50
9.52 9.52 (±0.03) 9.62 ( ) 8 7 0.08 or less 0.60
12.70 12.70 (±0.03) 12.81 ( ) 9 8 0.10 or less 0.70
15.88 15.88 (±0.03) 16.00 ( ) 9 8 0.13 or less 0.80
19.05 19.05 (±0.03) 19.19 ( ) 11 10 0.15 or less 0.80
22.22 22.22 (±0.03) 22.36 ( ) 11 10 0.16 or less 0.82
28.58 28.58 (±0.04) 28.75 ( ) 13 12 0.20 or less 1.00
34.92 34.90 (±0.04) 35.11 ( ) 14 13 0.25 or less 1.20
38.10 38.10 (±0.05) 38.31 ( ) 15 14 0.27 or less 1.26
41.28 41.28 (±0.05) 41.50 ( ) 15 14 0.28 or less 1.35
K
ØC
G
ØF
+0.04
-0.02
+0.04
-0.02
+0.04
-0.02
+0.04
-0.02
+0.03
-0.03
+0.03
-0.03
+0.06
-0.02
+0.04
-0.04
+0.08
-0.02
+0.08
-0.02
Table 1
Table 2
* For combination of the outdoor units, refer to “Combination of outdoor units”.
Indoor unit
capacity rank
Capacity code
Equivalent to HP
Equivalent to
capacity
007 0.8 2.2
009 1 2.8
012 1.25 3.6
015 1.7 4.5
018 2 5.6
024 2.5 7.1
027 3 8
030 3.2 9
036 4 11.2
048 5 14
056 6 16
072 8 22.4
096 10 28
Outdoor unit
model name
(Standard model)
Capacity code
No. of
indoor
units
Outdoor unit
model name
(High Efficiency
model)
Capacity code
No. of
indoor
units
Equivalent to
HP
Equivalent to
capacity
Equivalent to
HP
Equivalent to
capacity
MMY-MAP0804 822.413— — —
MMY-MAP1004 10 28 16
MMY-MAP1204 12 33.5 20
MMY-MAP1404 14 40 23
MMY-MAP1604 16 45 27 MMY-AP1624 16 45 27
MMY-AP1814 18 50.4 30
MMY-AP2014 20 56 33
MMY-AP2214 22 61.5 37
MMY-AP2414 24 68 40 MMY-AP2424 24 68 40
MMY-AP2614 26 73 43 MMY-AP2624 26 73 43
MMY-AP2814 28 78.5 47 MMY-AP2824 28 78.5 47
MMY-AP3014 30 85 48 MMY-AP3024 30 85 48
MMY-AP3214 32 90 48 MMY-AP3224 32 90 48
MMY-AP3414 34 96 48 MMY-AP3424 34 96 48
MMY-AP3614 36 101 48 MMY-AP3624 36 101 48
MMY-AP3814 38 106.5 48 MMY-AP3824 38 106.5 48
MMY-AP4014 40 112 48 MMY-AP4024 40 112 48
MMY-AP4214 42 118 48 MMY-AP4224 42 118 48
MMY-AP4414 44 123 48 MMY-AP4424 44 123 48
MMY-AP4614 46 130 48 MMY-AP4624 46 130 48
MMY-AP4814 48 135 48 MMY-AP4824 48 135 48
21-EN 22-EN
+00EH99871699_01EN.book Page 11 Thursday, August 26, 2010 4:41 PM