All installations and services must be performed by qualified service personnel.
8. As a final step in the installation, the appliance must be adjusted to deliver a
temperature rise within the range of 50° to 80°F. Adjust the blower motor
speed to obtain a temperature rise within the acceptable range. The required
blower speed will depend on the airflow resistance of a supply and return air
duct systems.
I. Air Filters
1. Filter Installation
This OPB unit has been factory supplied with a high quality, re-usable filter
rated for air velocities up to 600 ft/min.
2. Use of non-Thermo Pride Filters or Retention Means
: Failure to comply with minimum filter installation
requirements may affect the performance and/or void the warranty on
this unit.
If a method other than Thermo Pride filter racks is selected for retention of the
filter and/or use of a different filter type is desired, refer to Table 4 for
minimum sizing guidelines for selecting filter for the unit.
Table 4: Minimum Required Filter Area (in square inches)
Model Number
Filter Type
Maximum
Air Velocity
(ft/min)
OPB24 OPB30 OPB36
*Thermo Products
Supplied
Permanent
600
192
240
288
Standard
Permanent
500 230 288 346
Disposable 300 384 480 576
The Thermo Products supplied filter can be cut to size to fit other filter
retention systems as long as the minimum size requirement is met.
NOTICE: Any internal stiffeners used in the filter must not be removed,
although they can be cut to size as needed.