SMD Series Dehumidifying Dryers Page 25
CAUTION!
• Use caution and observe safety rules when lifting and placing
your dryer!
Figure 4
Suggested Lift Rigging for SMD Dryers (Floor Mount)
Note: Floor Mounted Dryers can be lifted by hoist or fork lift.
4-3 Making Electrical Connections
; The serial tag lists voltage, phase, and amp draw information.
; Line voltage must be within plus or minus ten percent (±10%)
of the voltage listed on the serial tag, or damage may occur.
Phase imbalance must be less than two percent (2%).
; Fulfill all national, state, and local safety and electrical code
requirements.
; A qualified electrician should make all electrical connections.
; Make sure all electrical connections are tight.
; Connect main power to the dryer at the disconnect or terminals
in the upper right corner of the control enclosure.
; Install a fused disconnect with a lockout feature in the power
main leading to the dryer.
; The power drop must include a ground wire.