Schneider Electric iEM3300 Indoor Furnishings User Manual


 
iEM3100 / iEM3200 / iEM3300 series user manual Specifications
DOCA0005EN-04 99
Mechanical characteristics
Environmental characteristics
Measurement accuracy
Programmable digital
input
Number
2 iEM3115 / iEM3215
1
iEM3135 / iEM3155 / iEM3165 /
iEM3175 / iEM3235 / iEM3255 /
iEM3265 / iEM3275 / iEM3335 /
iEM3355 / iEM3365 / iEM3375
Type Type 1 (IEC 61131-2)
iEM3115 / iEM3135 / iEM3155 /
iEM3165 / iEM3175 / iEM3215 /
iEM3235 / iEM3255 / iEM3265 /
iEM3275 / iEM3335 / iEM3355 /
iEM3365 / iEM3375
Maximum input
Voltage 40 V DC
Current 4 mA
Voltage OFF 0 - 5 V DC
Voltage ON 11 - 40 V DC
Nominal voltage 24 V DC
Isolation 3.75 kV rms
Wire 1.5 mm
2
/ 16 AWG
Wire strip length 6 mm / 0.23 in
Torque 0.5 Nm / 4.4 in•lb
Characteristic Value Meters
Characteristic Value Meters
IP degree of protection
Front panel
IP40
iEM31•• / iEM32•• / iEM33••
Meter body
IP20
Impact rating IK08 iEM31•• / iEM32•• / iEM33••
Active energy display range
In kWh or MWh up to 99999999 MWh iEM32••
In kWh: 8 + 1 digits up to 99999999.9 iEM31•• / iEM33••
Energy pulsing LED (yellow)
1
500 flashes / kWh iEM31••
5000 flashes / kWh without consideration of transformer ratios iEM32••
200 flashes / kWh iEM33••
1
The pulses / kWh of the energy pulsing LED cannot be changed.
Characteristic Value Meters
Operating temperature -25 °C (-13 °F) to +55 °C (131 °F) (K55)
iEM31•• / iEM32•• / iEM33••
Storage temperature -40 °C (-40 °F) to +85 °C (185 °F)
Pollution degree 2
Relative humidity
5% – 95% RH non-condensing
Maximum dewpoint 50 °C (122 °F)
Location
For indoor use only
Not suitable for wet locations
Altitude < 2000 m (6561 ft) above sea level
Characteristic Value Meters
63 A
Active energy
Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD):
I
max
=63 A, I
b
=10 A, and I
st
=0.04 A
iEM31••
Class B conforming to EN 50470-3: I
max
=63 A, l
ref
=10 A, I
min
=0.5 A, and
I
st
=0.04 A
iEM31••
Reactive energy
Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD):
I
max
=63 A, I
b
=10 A, and I
st
=0.05 A
iEM3135 / iEM3155 / iEM3165 / iEM3175
125 A
Active energy
Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD):
I
max
=125 A, I
b
=20 A, and I
st
=0.08 A
iEM33••
Class B conforming to EN 50470-3: I
max
=125 A, l
ref
=20 A, I
min
=1 A, and
I
st
=0.08 A
iEM33••
Reactive energy
Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD):
I
max
=125 A, I
b
=20 A, and I
st
=0.1 A
iEM3335 / iEM3355 / iEM3365 / iEM3375