Hardware and installation iEM3100 / iEM3200 / iEM3300 series user manual
125 A direct measurement meter wiring
Fuses and disconnect switch
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not connect N’ to the load when setting the wiring type on the meter to 1PH4W Multi L-N.
Failure to follow these instructions will result in death or serious injury.
Power system Wiring
1PH multiple loads with neutral (1PH4W Multi L-N)
1
1
The 1PH4W Multi L-N wiring type is only available on the iEM3135, iEM3150, iEM3155, iEM3165 and iEM3175.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not allow the total additive current flowing through the device to exceed 125 A.
Failure to follow these instructions will result in death or serious injury.
Power system Wiring
1PH2W L-N
1PH2W L-L
1PH3W L-L-N
3PH3W
NN L3L2’L2L1’L1 L3’
L
N
NN L3L2’L2L1’L1 L3’
277 V L-N
L
N
NN L3L2’L2L1’L1 L3’
277 V L-N
L1
L2
NN L3L2’L2L1’L1 L3’
480 V L-L
L1
L2
NN L3L2’L2L1’L1 L3’
N
277 V L-N
480 V L-L
L1
L2
NN L3L2’L2L1’L1 L3’
N
277 V L-N
480 V L-L
L1
L2
NN L3L2’L2L1’L1 L3’
L3
480 V L-L