Schneider Electric iEM3300 Indoor Furnishings User Manual


 
94 DOCA0005EN-04
Communications via BACnet iEM3100 / iEM3200 / iEM3300 series user manual
Communications settings information
The following AI objects display information about the meter’s communications settings.
NOTE: You can access the meter’s communications configuration information over BACnet
communications. However, you must use the front panel to configure the meter’s settings.
Digital input and output setting information
The following AI objects display information about the meter’s I/O settings.
NOTE: You can access the meter’s I/O configuration information over BACnet communications.
However, you must use the front panel to configure the meter’s settings.
Related topics
See “Device configuration” on page 38 for information on configuring the meter using the front
panel.
See “Binary Input objects” on page 95 for information on reading the statuses of the input, output
and alarm.
54 A 1
AI54 - CT Secondary
NOTE: only applies to the iEM3265
55 1
AI55 - VT connection type
0 = Direct connection, not VTs
1 = 3PH3W (2VTs)
2 = 3PH4W (3VTs)
Object ID Units Default COV Object name / description
00 1 AI00 - BACnet MAC Address
01 1 AI01 - BACnet Baud Rate
Object ID Units Default COV Object name / description
02 ms 1
AI02 - Pulse Duration
The energy pulse duration (or pulse width), in milliseconds, of the digital
output.
NOTE: This information only applies if the digital output mode is set to
energy pulsing.
03 1
AI03 - Pulse Weight
The pulses/unit setting of the digital input when it is configured for input
metering.
NOTE: This information only applies if the digital input mode is set to
Input Metering.
04 1
AI04 - Pulse Constant
The pulses/kWh setting of the digital output.
NOTE: This information only applies if the digital output mode is set to
energy pulsing.
05 1
AI05 - Digital Input Mode
0 = Normal (input status)
2 = Multi Tariff control
3 = Input metering
5 = All partial energy logs reset
06 1
AI06 - Digital Output Mode
2 = Alarm
3 = Energy
0xFFFF (65535 dec) = Disabled
42 kW 10
AI42 - Pickup Setpoint
Active power alarm pickup setpoint in kW
43 kW 10 AI43 - Last Alarm Value