92 DOCA0005EN-04
Communications via BACnet iEM3100 / iEM3200 / iEM3300 series user manual
Related topics
See “Device configuration” on page 38 for information on configuring the meter using the front
panel.
Analog Input objects
The following tables list the Analog Input (AI) objects along with the units and default COV value for
each AI object (if applicable).
NOTE: The Value Type for all AI objects is Real.
Energy and energy by tariff measurements
The energy and energy by tariff measurements listed below are preserved through power failures.
Local_Time R configurable
Time
NOTE: You must use the front panel to set the meter’s time.
APDU_Timeout R/W 1000 - 30000
The amount of time (in milliseconds) before the meter tries to resend a confirmed
message that has not been answered.
Number_Of_APDU_Retries R/W 1 - 10
The number of times the meter tries to resend an unanswered confirmed
request.
Max_Master R/W 1 - 127
The highest master address the meter will try to discover when the next node is
unknown.
Max_Info_Frames R/W 1 - 14
Maximum number of messages the meter can send before it must pass the
token.
Device_Address_Binding R
Device address binding table is always blank because the meter does not initiate
the who-Is service.
Database_Revision R varies
A number that increments when the object database on the meter changes (for
example, when an object is created or deleted or the ID of an object changes).
Active_COV_Subscriptions R varies List of COV subscriptions currently active on the meter.
Profile_Name R varies
Device identifier, used on these meters to record the meter manufacturer, the
meter family and the specific meter model (for example, 10_iEM3000_iEM3265).
ID 800 R varies Date and time of last energy reset
ID 801 R varies Date and time of last input metering accumulation reset
ID 802 R varies Date and time of the last alarm (DD/MM/YYYY hh:mm:ss)
Device object property R/W Stored Possible values Description
Object ID Units Default COV Object name / description
27 Wh 100 AI27 - Total active energy import
28 Wh 100 AI28 - Total active energy export
29 Wh 100 AI29 - Total reactive energy import
30 Wh 100 AI30 - Total reactive energy export
31 Wh 100 AI31 - Partial active energy import
32 Wh 100 AI32 - Partial reactive energy import
33 Wh 100 AI33 - Active energy import phase 1
34 Wh 100 AI34 - Active energy import phase 2
35 Wh 100 AI35 - Active energy import phase 3
36 10
AI36 - Accumulation
Input metering accumulation
37 1
AI37 - Tariff Energy Active Rate
Denotes the active tariff:
0 = Multi Tariff feature is disabled
1 = rate A (tariff 1) active
2 = rate B (tariff 2) active
3 = rate C (tariff 3) active
4 = rate D (tariff 4) active
38 Wh 100 AI38 - Rate A (Tariff 1) active energy import
39 Wh 100 AI39 - Rate B (Tariff 2) active energy import
40 Wh 100 AI40 - Rate C (Tariff 3) active energy import
41 Wh 100 AI41 - Rate D (Tariff 4) active energy import