DOCA0005EN-04 69
Basic setup
Digital input setup
Input metering setup
Function profile UCPT Struct Members Range / options Description
nciCfgWiring UCPTWiring
SystemType 0, 1, 2, 3, 11, 13
0 = 1PH2W L-N
1 = 1PH2W L-L
2 = 1PH3W L-L with N
3 = 3PH3W
11 = 3PH4W
13 = 1PH4 wire multi L with N
NominFreq 50, 60 Nominal frequency in Hz
VtPrimary 0 - 1000000.0
The minimum value for VtPrimary
must be equal to or greater than
the value set for VtSecondary.
VtSecondary 100, 110, 115, 120
CtNum 1, 2, 3
CtPrimary 1 - 32767
CtSecondary 1, 5
VtConnType 0, 1, 2
VT connection type
0 = Direct connection
1 = 3PH3W (2VTs)
2 = 3PH4W (3VTs)
Function profile UCPT Struct Members Range / options Description
nciCfgDigitInpt UCPTDigitalInput 0, 1
Associates the digital input to reset partial
energy data:
0 = Digital input is not associated with the
partial energy reset.
1 = Digital input is associated with the partial
energy reset.
Setting this property to 1 also updates
nciDICtrlMode (UCPTDiCtrlMode) to All
Energy Reset.
Function profile UCPT Struct Members Range / options Description
nciCfgInptMetAcc UCPTInputMetering
PulseWeight 1 - 10000
Sets the pulse weight (1 - 10000 ms)
Setting this property also sets
nciDIPulseConst (UCPTDiPulseConst) to
the same value.
DigitalAssociation 0, 1
Associates the digital input with input
metering:
0 = Digital input is not associated with input
metering.
1 = The digital input is associated with input
metering.
Setting this property to 1 also updates
nciDICtrlMode (UCPTDiCtrlMode) to Input
Metering.