Communications via M-Bus iEM3100 / iEM3200 / iEM3300 series user manual
Manufacturer-specific VIFE codes
The manufacturer-specific VIFE codes in the table below are used by the meter when the VIF equals
FF hex (1111 1111 bin).
NOTE: E denotes the extension bit; the hex value assumes E = 0.
Cumulation counter E110 0001 x1 Input metering accumulation
Error flag E001 0111 x7
Description bin hex
L1 value E000 0001 01
L2 value E000 0010 02
L3 value E000 0011 03
Export energy value E000 1001 09
Partial energy value E000 1101 0D
Average current E000 0000 00
L-N Avg E000 0100 04
L1-L2 E000 0101 05
L2-L3 E000 0110 06
L3-L1 E000 0111 07
L-L Avg E000 1000 08
Power Factor E000 1010 0A
Frequency E000 1011 0B
Energy reset date and time E000 1100 0C
Input metering reset date and time E000 1110 0E
Input metering accumulation E000 1111 0F
Active tariff (Energy active rate) E001 0000 10
Tariff control mode E001 0001 11
Meter operation timer E010 0000 20
Number of phases E010 0001 21
Number of wires E010 0010 22
Power system configuration E010 0011 23
Nominal frequency E010 0100 24
Number of VTs E010 0101 25
VT primary E010 0110 26
VT secondary E010 0111 27
Number of CTs E010 1000 28
CT Primary E010 1001 29
CT Secondary E010 1010 2A
VT connection type E010 1011 2B
Energy pulse duration E010 1100 2C
Digital output association with active energy pulsing E010 1101 2D
Pulse weight E010 1110 2E
Pulse constant E010 1111 2F
Digital input association E011 0000 30
Digital input status E011 0010 32
Overload alarm setup E011 0100 34
Pickup setpoint E011 0101 35
Digital output association with overload alarm E011 0110 36
Activated status E011 0111 37
Acknowledgement E011 1000 38
Date and time of last alarm E011 1001 39
Value at last alarm E011 1010 3A
Primary VIFE codes bin hex Additional information