Auto Reset Temperature Limiting
Model CS-7L
Rating AC125V, 200mA
Thermal Fuse
Model X25
Cut-off temp. 293°F (145°C)
Transformer (TR) 4FF4L510034000
Rating Primary AC 115V, 60Hz
Secondary S1 DC 25.4V, 0.25A
S2 DC 12.6V, 0.1A
S3 AC 100V, 1Ma
Capacity 5VA
Coil resistance (at 70°F (21°C)) Primary (ORG – ORG): 71.1 ± 10%
Secondary (RED – RED): 5.79 ± 10%
Secondary (BLU – BLU): 8.38 ± 10%
Secondary (YEL – YEL): 257 ± 10%
Thermal cut-off temp. 277°F (136°C)
Thermistor 1 (Discharge pressure) PB3M-41E
Resistance k 122°F (50°C) 2.2 ± 5%
Thermistor 2 (Outlet refrigerant temp.) PB3M-41E
Resistance k 131°F (55°C) 2.2 ± 5%
Reversing Valve CHV-01AE (Coil), CHV-0101 (Valve)
Coil rating AC115 – 120V, 50/60Hz, 6/5W
Coil resistance 370
ON/OFF Valve (Q’ty = 2) NEV-MOAE (Coil), NEV-603DXF (Valve)
Coil rating AC115 – 120V, 50/60Hz, 7W
Coil resistance 370
2-3-2. Outdoor Unit
Outdoor unit CG1411
Power Relay (PR) DFU24D1F
Coil rating DC 24V
Coil resistance (at 68°F (20°C)) 650 ± 10%
Contact rating AC 250V, 20A
Check Valve 1 (See Refrigerant Diagram) FCV-3020D
Check Valve 2 (See Refrigerant Diagram) BCV-804DX