Raypak 992A-2342A Fan User Manual


 
47
Direct Vent - Vertical
Vertical Venting
Height*
Air Inlet
Max. Length**
Model
Certified
Venting
Material
Vent Size
Min. Max.
Combustion Air
Intake Pipe
Material
10” 12”
992AE 10”
1262AE
1532AE
12”
75’ 100’
1802AE
2002AE
2072AE
14”
2342AE
Category II
or IV
16”
5’ 25’
Galvanized Steel,
PVC,
ABS,
CPVC
40’ 75’
* Vent lengths are based on a lateral length of 2 ft. Refer to the latest edition of the NFGC for further details.
When vertical height exceeds 25 ft, consult factory prior to installation.
** Subtract 10 ft per elbow. Max. 3 elbows.
Maximum combustion air duct length terminated at 100 equivalent ft.
Note: When vertical height exceeds 25 ft, consult
factory prior to installation.
Fig. 43: Direct Vent - Vertical
Table R: Category II or IV Vertical Venting