Quadra-Fire DV-40 Indoor Fireplace User Manual


 
Page 9
Thermostat
Connection
THERMOSTAT INSTALLATION
If desired, a thermostat may be installed to regulate the Quadra-Fire DV-40 Step. It is important to use a
thermostat designed for millivolt operation. Do not connect this stove to a thermostat serving any other
appliance. Bedroom installation in Canada requires this stove to be hooked to a thermostat.
OPTIONAL THERMOSTATS
Manual Thermostat
Part #812-2880
Anticipator Setting 1.2
Programable Thermostat
Part #811-0520
RECOMMENDED MAXIMUM LEAD
LENGTH (TWO WIRE) WHEN USING
WALL THERMOSTAT/SWITCH
Wire Size Maximum Length
16 gauge 65 feet
18 gauge 40 feet
20 gauge 25 feet
22 gauge 18 feet
Connect the thermostat wires to the outside terminals labled TH and THTP located on the valve. Turn
off the manual switch, located on the control panel.
REMOTE CONTROL
A remote control or a wall switch may be wired to the thermostat terminals. Contact your Quadra-Fire
dealer or service person for details (see page 45 for part number).
BLOWER POWER CORD
The blower cord is located at the rear of the stove, and needs to be routed to a three-prong outlet with
correct polarity. Be sure that the stove is electrically grounded in accordance with local codes, with a
current version of CSA C22.2 No. 3 M1988 (in Canada), or in the absence of local codes, with the National
Electric Code ANSI/NFPA 70-1987.
WARNING
Do not cut the grounding terminal off under any circumstances.
Do not route the power cord under the body of the stove due to high temperatures.