Quadra-Fire DV-40 Indoor Fireplace User Manual


 
Page 19
HORIZONTAL INSTALLATION (CONT.)
Step 3. With the adapter and pipe attached to the stove, slide the stove into its correct location, maintaining
minimum clearance to combustibles, and mark the wall for a 10 x 10 (254mm x 254mm) square
hole. The center of the square hole should line up with the centerline of the horizontal pipe, as
shown in Figure 6. Cut and frame the hole in the exterior wall where the vent will be terminated.
If the wall being penetrated is constructed of noncombustible material, i.e. masonry block or
concrete, a 7 (178mm) diameter hole is acceptable.
NOTE:
(1) The horizontal run of vent must be level, or have a ¼” (6mm) rise for every 1 (305mm) of run
towards the termination. Never allow the vent to run downward. This could cause high temperatures
and may present the possibility of a fire.
(2) The location of the horizontal vent termination on an exterior wall must meet all local and national
building codes, and must not be easily blocked or obstructed.
(3) For installations requiring a vertical rise on the exterior of the building, 14 (356mm) and 36
(914mm) tall snorkel terminations are available. Follow the same installation procedures as used
for standard horizontal terminations. If the snorkel termination must be installed below grade (i.e.
basement application), proper drainage must be provided to prevent water from entering the
snorkel termination. Do not backfill around snorkel termination.
NOTE: With proper vertical rise, refer to Venting Graph on page 15, up to four, 90 degree elbows may be
used.
Minimum vertical rise in a horizontal venting installation is 2’ (two feet). (See Venting Graph,
page 15.)
CENTER LINE
CENTER
LINE
CENTER OF HOLE
FIG. 6
Note: USE THE FOLLOWING
HORIZONTAL TERMINATION CAPS
ONLY!
1) Simpson DuraVentPart #985
OR
2) Aladdin Hearth Products Part
#HHW2