43
GAS-FIRED BOILER Boiler Manual
VIEW
TOP VIEW
AND VERTICAL PIPING
SUPPORT BRACKETS
MUST BE USED ON
ALL HORIZONTAL
VENT KIT
RIGHT SIDE
EXTERIOR WALL
NOTE: EXTENDED VENT
RUNS WHEN TRANSITIONING
TO A LARGER DIAMETER
MUST ALWAYS TAKE PLACE
IN A VERTICAL POSITION
TO PREVENT CONDENSATE
BLOCKAGE.
SIDWALL
VENTING
WITH
KIT
VENT KIT
INTAKE AIR
VENT
EXHAUST
VENT
EXTERIOR WALL
INTAKE AIR
VENT
SIDEWALL VENTING WITH KIT
RIGHT SIDE VIEW
AND VERTICAL PIPING
VENT KIT
ALL HORIZONTAL
SUPPORT BRACKETS
MUST BE USED ON
EXHAUST
VENT
Figure 7-11
Figure 7-12
SIDEWALL VENTING WITH
CONCENTRIC VENT KIT
AND VERTICAL PIPING
ALL HORIZONTAL
EXTERIOR WALL
VENT
EXHAUST
RIGHT SIDE VIEW
MUST BE FACING UP
NOTE: INTAKE LEG
SUPPORT BRACKETS
MUST BE USED ON
INTAKE AIR
VENT
1" MIN.
AND VERTICAL PIPING
FRONT VIEW
EXTERIOR WALL
MUST BE FACING UP
ALL HORIZONTAL NOTE: INTAKE LEG
EXHAUST
VENT
SUPPORT BRACKETS
MUST BE USED ON
INTAKE AIR
VENT
1" MIN.
SIDEWALL VENTING WITH
CONCENTRIC VENT KIT
GENERAL NOTE: All vent pipes must be glued, properly supported and the exhaust must be pitched a
minimum of a ¼" per foot back to the heater (to allow drainage of condensate).
NOTE: When placing support brackets on vent piping, the first bracket must be within 1 foot of the
appliance and the balance at 4 foot invervals on the vent pipe. The boiler venting must be readily
accessible for visual inspection for the first three feet from the boiler.