Munchkin Gas-Fired Hot Water Boiler Boiler User Manual


 
31
GAS-FIRED BOILER Boiler Manual
Munchkin VISION 1 system
(zoning with circulators)
Space heating mode (w/ submixing)
NOTES:
1.
This drawing is meant to show system piping concept only.
Installer is responsible for all equipment & detailing required by local codes.
2. All closely spaced tees shall be within 4 pipe diameter center to center spacing.
3.
A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream
of all closely spaced tees.
4.
The minimum pipe size for connecting a Super Stor water heater is 1 inch.
5. The minimum pipe size for connecting a Munchkin boiler shall be 1.25 inches and 2 inches for the 399M.
6.
All pumps are shown with isolation flanges and integral flow check valves.
The alternative is standard flanges with full port ball valves and a separate flow check valve.
7.
The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.
8. Install a minimum of 12 diameters of straight pipe upstream of all circulators.
9.
A purging valve may be used in lieu of the ball valve / hose bib combination shown.
10. Adjust 3-way manually-set mixing valve to yield proper supply temperature to lower temperature load.
Drawing 4C
Munchkin boiler
DHW
temperature
sensor
purge
Super Stor
indirect DHW tank
anti-scald mixing valve
outdoor
temperature
sensor
thermal trap
(w/ drain plug)
high limit safety
air handler
vent
3-way
(manually-set)
mixing valve
low temperature
manifold station
P1
P2
balancing
valve
T/P
OFF
purge
make-up water
cold
water
purge