33
GAS-FIRED BOILER Boiler Manual
Munchkin VISION 1 system
(zoning with circulators)
Space heating mode (3 different supply temperatures)
NOTES:
1.
This drawing is meant to show system piping concept only.
Installer is responsible for all equipment & detailing required by local codes.
2.
All closely spaced tees shall be within 4 pipe diameter center to center spacing.
3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream
of all closely spaced tees.
4. The minimum pipe size for connecting a Super Stor water heater is 1 inch.
5.
The minimum pipe size for connecting a Munchkin boiler shall be 1.25 inches and 2 inches for the 399M.
6. All pumps are shown with isolation flanges and integral flow check valves.
The alternative is standard flanges with full port ball valves and a separate flow check valve.
7.
The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.
8. Follow all instructions for installation of injection mixing system.
9.
A purging valve may be used in lieu of the ball valve / hose bib combination shown.
10. Adjust 3-way manually-set mixing valve to yield proper supply temperature to lower temperature load.
Drawing 4F
Munchkin boiler
DHW
temp.
sensor
purge
Super Stor
indirect DHW tank
anti-scald
mixing valve
outdoor
temperature
sensor
thermal trap
(w/ drain plug)
high limit safety
air handler
(higher temp.)
vent
low temperature
manifold station
P1
P2
T/P
OFF
vent
medium
temperature
manifold station
balancing
valves
variable
speed
injection
mixing
3-way manually-set
mixing valve
purge
make-up water
purge
make-up water
cold
water
purge