Monessen Hearth CDVR33N/PV7;N/PE7;N/PSC7 Indoor Fireplace User Manual


 
CDVSC7 & CDV7 Series Gas Fireplace
69D3011
5
For the minimum height of the vent above the highest
point of penetration through the roof refer to Figure 38,
Page 6.
Max. Height 40’ (1. m)
Min. Height 8’ (.4 m)
Max. 10’ (3 m)
Support Straps
Every 3’ (.9 m)
Max.
Height 40’ (1. m)
Min.
Height 8’ (.4 m)
Max. 10’ (3 m)
FP1183
Figure 33 -
Support Straps for
Horizontal Runs
1
2
3
4
1
2
3
4
FP1179
Figure 34 -
Maximum Elbow Usage
1 +  + 3 + 4 = 70°


 For all top vent vertical through-the-roof installa-
tions, install the supplied cross-bar flue restrictor onto the
top edge of the firebox flue adapter. Figure 35
1. Locate your fireplace.
. Plumb to center of the (4”) flue
collar from ceiling above and
mark position.
3.
Cut opening equal to 9C\v” x
9C\v” (48 x 48 mm).
4. Proceed to plumb for addi-
tional openings through the
roof. In all cases, the
opening must provide
a
minimum of 1 inch
clearance to the vent
pipe, i.e., the hole must
be at least 9C\v” x 9C\v” (48 x 48 mm).
5. Place fireplace into position.
6. Place firestop(s) or Attic Insulation Shield into position
and secure. Figure 36
FP1029
attic insulation shield
firestop spacers
1/28/00 djt




11”
(79 mm)

Joist
Firestop
Spacer
Nails (4)
FP109
Figure 36 -
Place Firestop Spacer(s) and Secure

FP2304
CDV7 top restrictor
3/09
Figure 35 -
Vertical Through-the-Roof
Restrictor
FP304
7. Install roof support (Figure 37) and roof flashing mak-
ing sure upper flange is below the shingles. Figure 39
8. Install appropriate pipe sections until the venting is
above the flashing. Figure 39