Mitsubishi P192 Air Conditioner User Manual


 
[ II Restrictions ]
35- 35 -
HWE09120 GB
(4) Wiring method
1) Indoor/outdoor transmission line
Same as [5] 1.
Only use shielded cables.
Shielded cable connection
Same as [5] 1.
2) Transmission line for centralized control
Daisy-chain terminals A and B on the system controller,
terminals M1 and M2 on the terminal block for transmis-
sion line for centralized control (TB7) on the outdoor
units (OC) in different refrigerant circuits and on the out-
door units (OC, OS1, and OS2) in the same refrigerant
circuit. (Note b)
If a power supply unit is not connected to the transmis-
sion line for centralized control, replace the power jump-
er connector on the control board from CN41 to CN40 on
only one of the outdoor units.
If a system controller is connected, set the central control
switch (SW2-1) on the control board of all outdoor units
to "ON."
a) The outdoor units in the same refrigerant circuit are auto-
matically designated as OC, OS1, and OS2 in the order
of capacity from large to small (if two or more units have
the same capacity, in the order of address from small to
large).
b) When not daisy-chaining TB7's on the outdoor units in
the same refrigerant circuit, connect the transmission
line for centralized control to TB7 on the OC (Note a). To
maintain centralized control even during an OC failure or
a power failure, daisy-chain TB7 of OC, OS1, and OS2.
(If there is a problem with the outdoor unit whose power
jumper was moved from CN41 to CN40, centralized con-
trol is not possible, even if TB7's are daisy-chained).
Only use shielded cables.
Shielded cable connection
Daisy-chain the S terminal on the terminal block (TB7) on
the outdoor units (OC, OS1, OS2) with the shield wire of
the shielded cable. Short-circuit the earth terminal ( )
and the S terminal on the terminal block (TB7) on the out-
door unit whose power jumper connector is mated with
CN40.
3) MA remote controller wiring
Same as [5] 1.
When 2 remote controllers are connected to the sys-
tem
Same as [5] 1.
Group operation of indoor units
Same as [5] 1.
4) LOSSNAY connection
Connect terminals M1 and M2 on the terminal block
(TB5) on the indoor unit (IC) to the appropriate terminals
on the terminal block for indoor-outdoor transmission line
(TB5) on LOSSNAY (LC). (Non-polarized 2-core cable)
Indoor units must be interlocked with the LOSSNAY unit
using the system controller. (Refer to the operation man-
ual for the system controller for the setting method.) In-
terlock setting from the remote controller is required if the
ON/OFF remote controller alone or the LM adapter alone
is connected.
5) Switch setting
Address setting is required as follows.
(5) Address setting method
The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2.
The outdoor units are designated as OC, OS1, and OS2 in the order of capacity from large to small (if two or more units have
the same capacity, in the order of address from small to large).
Proce-
dures
Unit or controller
Address
setting
range
Setting method Notes
Factory
setting
1 Indoor unit Main unit IC 01 to 50 Assign the smallest address
to the main unit in the group.
To perform a group oper-
ation of indoor units that
have different functions,
designate the indoor unit
in the group with the
greatest number of func-
tions as the main unit.
00
Sub unit Assign sequential numbers
starting with the address of
the main unit in the same
group +1. (Main unit address
+1, main unit address +2,
main unit address +3, etc.)
2 LOSSNAY LC 01 to 50 Assign an arbitrary but
unique address to each of
these units after assigning
an address to all indoor units.
None of these addresses
may overlap any of the in-
door unit addresses.
00
3MA
remote
controller
Main
remote
control-
ler
MA No
settings re-
quired.
- Enter the same indoor
unit group settings on the
system controller as the
ones that were entered on
the MA remote controller.
Main
Sub
remote
control-
ler
MA Sub
remote con-
troller
Settings to be made accord-
ing to the remote controller
function selection
4 Outdoor unit OC
OS1
OS2
51 to 100 Assign sequential address to
the outdoor units in the same
refrigerant circuit.
The outdoor units are auto-
matically designated as OC,
OS1, and OS2. (Note)
To set the address to 100,
set the rotary switches to
50.
00