Mitsubishi P192 Air Conditioner User Manual


 
[ IX Troubleshooting ]
- 260 -
HWE09120 GB
INV board external diagram
Faston terminals have a locking function. Make sure the cable heads are securely locked in place. Press the tab on the ter-
minals to remove them.
Judgment value (reference)
Black ( + )
SC-P1 TB-N SC-R SC-S SC-T
Red (-)
SC-P1 - - 5 - 200 ohm 5 - 200 ohm 5 - 200 ohm
TB-N - -
SC-R 5 - 200 ohm - - -
SC-S 5 - 200 ohm - - -
SC-T 5 - 200 ohm - - -
Black ( + )
SC-P2 TB-N SC-U SC-V SC-W
Red (-)
SC-P2 - - 5 - 200 ohm 5 - 200 ohm 5 - 200 ohm
TB-N - -
SC-U 5 - 200 ohm - - -
SC-V 5 - 200 ohm - - -
SC-W 5 - 200 ohm - - -
SC-P1
SC-V
SC-W
SC-USC-RSC-SSC-TTB-N(Note)
SC-P2
[TJMU-A]