[ VIII Test Run Mode ]
- 145 -
HWE09120 GB
Operation
Outdoor unit model
PUHY-P264TSJMU-A
PUHY-P120TJMU-A PUHY-P144TJMU-A
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
21.1°C/ - [70°F/ - ]
Outdoor
8.3°C/6.1°C [47°F/43°F]
Indoor
unit
No. of connected
units
Unit
34
No. of units in opera-
tion 3 4
Model - 36/36/36 36/36/36/36
Piping
Main pipe
m [ft]
5 [16-3/8 ]
Branch pipe 10 [32-3/4 ]
Total pipe length 35 [114-13/16 ] 45 [147-5/8]
Fan speed - Hi
Amount of refrigerant
kg
[lbs-oz] 25 [55]
Outdoor
unit
Electric current A 67.4
Voltage V 230
Compressor frequency Hz 81 102
LEV open-
ing
Indoor unit
Pulse
332/332/332 332/332/332/332
SC (LEV1) 0 0
LEV2 2100 2100
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
MPa
[psi] 2.72/0.63 [395/91] 2.72/0.63 [395/91]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [°F]
70 [158] 89 [192]
Heat exchanger out-
let (TH3) -1 [30] -3 [27]
Accumulator inlet -1 [30] -3 [27]
Accumulator outlet -1 [30] -3 [27]
Compressor inlet -1 [30] -3 [27]
Compressor shell
bottom 40 [104] 40 [104]
Indoor
unit
LEV inlet 37 [98] 37 [98]
Heat exchanger
inlet 75 [166] 75 [166]