Mitsubishi P192 Air Conditioner User Manual


 
[ VIII Test Run Mode ]
- 146 -
HWE09120 GB
Operation
Outdoor unit model
PUHY-P288TSJMU-A
PUHY-P144TJMU-A PUHY-P144TJMU-A
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
21.1°C/ - [70°F/ - ]
Outdoor
8.3°C/6.1°C [47°F/43°F]
Indoor
unit
No. of connected
units
Unit
4
No. of units in opera-
tion 4
Model - 36/36/36/36
Piping
Main pipe
m [ft]
5[16-3/8]
Branch pipe 10 [32-3/4]
Total pipe length 45 [147-5/8]
Fan speed - Hi
Amount of refrigerant
kg
[lbs-oz] 27 [59]
Outdoor
unit
Electric current A 75.1
Voltage V 230
Compressor frequency Hz 102 102
LEV open-
ing
Indoor unit
Pulse
332/332/332/332 332/332/332/332
SC (LEV1) 0 0
LEV2 2100 2100
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
MPa
[psi] 2.74/0.61 [397/88] 2.74/0.61 [397/88]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [°F]
89 [192] 89 [192]
Heat exchanger out-
let (TH3) -3 [27] -3 [27]
Accumulator inlet -3 [27] -3 [27]
Accumulator outlet -3 [27] -3 [27]
Compressor inlet -3 [27] -3 [27]
Compressor shell
bottom 40 [104] 40 [104]
Indoor
unit
LEV inlet 37 [99] 37 [99]
Heat exchanger
inlet 80 [176] 80 [176]