[ VIII Test Run Mode ]
- 149 -
HWE09120 GB
Operation
Outdoor unit model
PUHY-P360TSJMU-A
PUHY-
P96TJMU-A
PUHY-
P120TJMU-A
PUHY-
P144TJMU-A
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
26.7°C/19.4°C [80°F/67°F]
Outdoor
35°C/ - [95°F/ - ]
Indoor
unit
No. of connected
units
Unit
7
No. of units in opera-
tion 7
Model - 48/48/48/54/54/54/54
Piping
Main pipe
m [ft]
5 [16-3/8 ]
Branch pipe 10 [32-3/4 ]
Total pipe length 75 [246-1/16]
Fan speed - Hi
Amount of refrigerant
kg
[lbs-oz] 33 [72]
Outdoor
unit
Electric current A 86.9
Voltage V 230
Compressor frequency Hz 65 74 97
LEV open-
ing
Indoor unit
Pulse
325/325/325/387/387/387/387
SC (LEV1) 171 171 171
LEV2 2100 2100 2100
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
MPa
[psi]
2.93/0.86 2.93/0.86 2.93/0.86
[425/125] [425/125] [425/125]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [°F]
74 [165] 73 [163] 82 [180]
Heat exchanger out-
let (TH3) 46 [115] 40 [104] 45 [113]
Accumulator inlet 10 [50] 10 [50] 7 [45]
Accumulator outlet 10 [50] 10 [50] 7 [45]
SCC outlet (TH6) 26 [79] 20 [68] 25 [77]
Compressor inlet 14 [57] 15 [59] 19 [66]
Compressor shell
bottom 38 [100] 42 [108] 38 [100]
Indoor
unit
LEV inlet 20 [69] 20 [69] 20 [69]
Heat exchanger
outlet 10 [50] 10 [50] 10 [50]